142
Table 5 — 30XA080-500 Electrical Data, Single Point (Standard Condenser Fan Motors) (cont)
LEGEND NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the control
power supply disconnect is on, even if any safety device is open.
3. For MCA
that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a
. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is 1/
0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
250 kcmil to 500 kcm
il.
5. Data provided circuit 1/circuit 2 where there are two circuits.
6. Standard condenser fan motors are not used with sizes 30XA-401, 451, 476, and 501.
These sizes use high ambient temperature condenser fans.
UNIT
30XA
UNIT VOLTAGE
NUMBER
OF
COND
FANS
10 HP PUMP, 3450 RPM 15 HP PUMP, 3450 RPM CONTROL CIRCUIT
V-Hz
(3 Ph)
Supplied
MCA MOCP
ICF Rec
Fuse
Size
MCA MOCP
ICF Rec
Fuse
Size
Voltage
1 PH,
60 Hz
MCA
and
MOCP
Min Max WD
XL WD XL
080,
082
230-60 207 253 6 115 40
200-60 187 220 6 115 40
460-60 414 506 6 115 40
575-60 518 633 6 115 40
380-60 342 418 6 115 40
090,
092
230-60 207 253 8 364.4 450 529.5 1215.5 400 379.0 500 544.1 1230.1 450 115 40
200-60 187 220 8 401.6 500 599.6 1388.6 450 417.7 500 615.8 1404.8 500 115 40
460-60 414 506 8 182.2 225 264.8 607.8 200 189.5 250 272.1 615.1 225 115 40
575-60 518 633 8 140.6 175 209.9 483.9 175 146.5 175 215.8 489.8 175 1
15 40
380-60 342 418 8 212.9 250 317.0 732.0 250 221.8 250 325.8 740.8 250 115 40
100,
102
230-60 207 253 8 395.0 500 567.1 1309.1 450 409.6 500 581.7 1323.7 450 115 40
200-60 187 220 8 434.9 500 641.5 1495.5 500 451.1 600 657.6 1511.6 500 115 40
460-60 414 506 8 197.5 250 283.6 654.6 225 204.8 250 290.9 661.9 225 115 40
575-60 518 633 8 151.7 200 223.8 520.8 175 157.5 200 229.7 526.7 175 115 40
380-60 342 418 8 231.1 300 340.1 789.1 300 239.9 300 348.9 797.9 300 115 40
110,
112
230-60 207 253 8 436.1
600 567.1 500 450.7 600 581.7 500 115 40
200-60 187 220 8 479.9 600 641.5 600 496.0 600 657.6 600 115 40
460-60 414 506 8 217.6 300 283.6 654.6 250 224.9 300 290.9 661.9 250 115 40
575-60 518 633 8 167.7 225 223.8 520.8 200 173.5 225 229.7 526.7 200 115 40
380-60 342 418 8 254.8 350 340.1 789.1 300 263.6 350 348.9 797.9 300 115 40
120,
122
230-60 207 253 8 469.0 600 600.0 600 483.6 600 614.6 600 115 40
200-60 187 220 8 515.8 700 677.4 600 531.9 700 693.5 600 115 40
460-60 414 506 8 233.6 300 29
9.6 670.6 300 240.9 300 306.9 677.9 300 115 40
575-60 518 633 8 180.5 225 236.7 533.7 200 186.4 250 242.5 539.5 225 115 40
380-60 342 418 8 273.7 350 359.0 808.0 300 282.6 350 367.9 816.9 350 115 40
140,
142
230-60 207 253 10 565.1 800 827.1 700 579.7 800 841.7 700 115 40
200-60 187 220 10 622.1 800 939.7 700 638.2 800 955.9 800 115 40
460-60 414 506 10 282.5 400 413.6 1045.6 350 289.8 400 420.9 1052.9 350 115 40
575-60 518 633 10 217.1 300 327.6 833.6 250 223.0 300 333.5 839.5 250 115 40
380-60
342 418 10 329.6 450 497.3 1262.3 400 338.5 450 506.2 1271.2 400 115 40
160,
162
230-60 207 253 10 651.5 800 1028.0 800 666.1 800 1042.6 800 115 40
200-60 187 220 10 716.4 1000 1169.7 1000 732.6 1000 1185.8 1000 115 40
460-60 414 506 10 324.9 450 513.6 1321.6 400 332.2 450 520.9 1328.9 400 115 40
575-60 518 633 10 250.2 350 408.5 1054.5 300 256.1 350 414.3 1060.3 300 115 40
380-60 342 418 10 379.5 500 617.3 1596.3 450 388.4 500 626.1 1605.1 450 115 40
180,
182
230-60 207 253 12 11
5 60
200-60 187 220 12 115 60
460-60 414 506 12 115 60
575-60 518 633 12 115 60
380-60 342 418 12 115 60
200,
202
230-60 207 253 12 115 60
200-60 187 220 12 115 60
460-60 414 506 12 115 60
575-60 518 633 12 115 60
380-60 342 418 12 115 60
220,
222
230-60 207 253 13 115 60
200-60 187 220 13 115 60
460-60 414 506 13 115 60
575-60 518 633 13 115 60
380-60
342 418 13 115 60
240,
242
230-60 207 253 13 115 60
200-60 187 220 13 115 60
460-60 414 506 13 115 60
575-60 518 633 13 115 60
380-60 342 418 13 115 60
260,
262
460-60 414 506 15 115 60
575-60 518 633 15 115 60
380-60 342 418 15 115 60
280,
282
460-60 414 506 16 115 60
575-60 518 633 16 115 60
380-60 342 418 16 115 60
300,
302
460-60 414 506 16 115 60
5
75-60 518 633 16 115 60
380-60 342 418 16 115 60
325,
327
460-60 414 506 18 115 60
575-60 518 633 18 115 60
380-60 342 418 18 115 60
350,
352
460-60 414 506 18 115 60
575-60 518 633 18 115 60
380-60 342 418 18 115 60
400
460-60 414 506 20 115 60
575-60 518 633 20 115 60
380-60 342 418 20 115 60
ICF Instantaneous Current Flow
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
WD Wye-Delta
XL Across-the-Line