Table 13 — Electrical Data — 30MPW050-071 Units without High Condensing Option
LEGEND
*Supply Range — Units are suitable for use on electrical systems
where voltage supplied to the unit terminals is not below or above
the listed range limits.
NOTES:
1. All units have one field power terminal block.
2. Maximum incoming wire size is as follows:
For units with terminal block:
500 kcmil for unit sizes 050-071; all voltages.
For units with optional non-fused disconnect:
350 kcmil for unit sizes 050-071, 208/230-3-60 voltages.
3/0 AWG for all other voltages.
3. Additional control circuit power is not required.
4. Any field modification of factory wiring must be in compliance
with all applicable codes. Field-installed power wires must be
rated 75°C minimum.
5. Use copper conductors only.
6. Control circuit power supply is 24-v single phase. Control power
is supplied by the factory-installed control transformer.
7. The MOCP of the electrical distribution panel is calculated as
follows:
First, calculate the MOCP of each individual chiller. MOCP =
2.25 (Largest RLA) + Sum of the other RLAs. Sum the MOCPs
of each individual chiller. This is the MOCP of the electrical dis-
tribution panel associated with this bank of chillers. Select the
next size down fuse from this value.
The recommended fuse size in amps (RFA) is calculated as fol-
lows: RFA = 1.50* (largest RLA) + (Smallest RLA) for the given
bank of chillers.
8. The MCA of the electrical distribution panel is calculated as
follows:
First, calculate the MCA of each individual chiller. MCA = 1.25
(Largest RLA) + sum of the other RLAs. Sum the MCAs of
each individual chiller. This is the MCA of the electrical distribu-
tion panel associated with this bank of chillers.
UNIT SIZE
30MPW
VOLTS
NAMEPLATE
VOLTAGE* COMPRESSOR A1 COMPRESSOR A2 UNIT
RLA LRA RLA LRA MCA ICF MOCP
REC
FUSE
MIN MAX
050
208/230-3-60 187 253 79.4 418 79.4 418 178.7 497.1 250 200
380-3-60 342 418
48.1 252 48.1 252 108.2 300.3 150 125
460-3-60 414 508
39.7 212 39.7 212 89.3 251.9 125 100
575-3-60 518 632
31.8 168 31.8 168 71.6 199.9 100 80
380/415-3-50 342 440
39.7 212 39.7 212 89.3 251.9 125 100
055
208/230-3-60 187 253 79.4 418 98.4 477 202.4 556.7 300 250
380-3-60 342 418
48.1 252 59.5 299 122.5 346.8 175 150
460-3-60 414 508
39.7 212 49.2 241 101.2 280.4 150 125
575-3-60 518 632
31.8 168 39.3 194 80.9 225.4 110 100
380/415-3-50 342 440
39.7 212 49.2 241 101.2 280.4 150 125
060
208/230-3-60 187 253 79.4 418 106.7 582 212.8 661.7 300 250
380-3-60 342 418
48.1 252 64.6 355 128.9 403.2 175 150
460-3-60 414 508
39.7 212 53.4 280 106.5 320.1 150 125
575-3-60 518 632
31.8 168 42.7 225 85.2 256.7 125 100
380/415-3-50 342 440
39.7 212 53.4 280 106.5 320.1 150 125
065
208/230-3-60 187 253 79.4 418 112.5 578 220.0 657.8 300 250
380-3-60 342 418
48.1 252 67.2 355 132.1 403.5 175 150
460-3-60 414 508
39.7 212 55.5 290 109.1 329.9 150 125
575-3-60 518 632
31.8 168 44.4 255 87.3 286.7 125 100
380/415-3-50 342 440
39.7 212 55.5 290 109.1 329.9 150 125
071
208/230-3-60 187 253 98.4 477 112.5 578 239.0 676.8 350 300
380-3-60 342 418
59.5 299 67.2 355 143.5 414.9 200 175
460-3-60 414 508
49.2 241 55.5 290 118.6 339.4 150 150
575-3-60 518 632
39.3 194 44.4 255 94.8 294.2 125 110
380/415-3-50 342 440
49.2 241 55.5 290 118.6 339.4 150 150
AWG American Wire Gage
ICF Maximum instantaneous current flow during starting.
kcmil Thousand circular mils
LRA Locked Rotor Amps
MCA Minimum Circuit Amps (for wire sizing). Complies with
NEC, Section 430-24.
MOCP Maximum Overcurrent Protection
Rec
Fuse
Recommended dual element fuse amps (150% of
compressor RLA). Size up to the next standard fuse
size.
RLA Rated Load Amps