unit PCB
Troubleshooting:
EE error will lock out the system and display 
EE until error is fixed or system restarted
If after parts replacement, error 
is still displayed, contact your 
local CE Technical Support Rep.
Is there standing water 
in drain pan?
No
Yes
No
Is drain line for 
clogged?
Yes
Replace PCB Pump 
is connected to.
Clear drain and 
restart system.
Water Level Alarm EE
Check float switch.
If stuck open, repair or replace.
Does internal or external 
drain pump have power to 
it during Cooling operation? 
CN13 220VAC
YesNo
Replace Pump.
40MBDQ09~58--3 Ducted
Follow the “1st Steps for DLS Troubleshooting” 
in the beginning of this guide, if you have an 
active error, procedure below.