Carrier ComfortLink 30GXN - Component Test; Mode: Service Test

Carrier ComfortLink 30GXN
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CL-8
Component Test Complete the following tests to make sure all peripheral components
are operational before the compressors are started.
MODE SERVICE TEST
To Enable Service Test Mode, move Enable/Off/Remote Contact
Switch to OFF. Configure TEST to ON. Move Switch to ENABLE.
SUB-MODE ITEM DISPLAY ITEM EXPANSION ENTRY
TEST ON/OFF SERVICE TEST MODE COMPLETE
OUTS EXV.A xxx % EXV % OPEN
VH.PA xxx % VAR HEAD PRESS %
OL.P.A ON/OFF OIL PUMP
MC.A1 ON/OFF MOTOR COOLING SOLENOID A1
MC.A2 ON/OFF MOTOR COOLING SOLENOID A2
OS.A1 ON/OFF OIL SOLENOID A1
OS.A2 ON/OFF OIL SOLENOID A2
EXV.B xxx % EXV % OPEN
VH.PB xxx % VAR HEAD PRESS %
OL.P.B ON/OFF OIL PUMP
MC.B1 ON/OFF MOTOR COOLING SOLENOID B1
MC.B2 ON/OFF MOTOR COOLING SOLENOID B2
OS.B1 ON/OFF OIL SOLENOID B1
OS.B2 ON/OFF OIL SOLENOID B2
FAN1 ON/OFF FAN 1 RELAY
FAN2 ON/OFF FAN 2 RELAY
FAN3 ON/OFF FAN 3 RELAY
FAN4 ON/OFF FAN 4 RELAY
CLR.P ON/OFF COOLER PUMP RELAY
CLR.H ON/OFF COOLER HEATER
CND.P ON/OFF CONDENSER PUMP RELAY
RMT.A ON/OFF REMOTE ALARM RELAY
COMP CC.A1 ON/OFF COMPRESSOR A1 RELAY
CC.A2 ON/OFF COMPRESSOR A2 RELAY
LD.A1 ON/OFF LOADER A1 RELAY
LD.A2 ON/OFF LOADER A2 RELAY
MLV ON/OFF MINIMUM LOAD VALVE
OL.H.A ON/OFF OIL HEATER
CC.B1 ON/OFF COMPRESSOR B1 RELAY
CC.B2 ON/OFF COMPRESSOR B2 RELAY
LD.B1 ON/OFF LOADER B1 RELAY
LD.B2 ON/OFF LOADER B2 RELAY
OL.H.B ON/OFF OIL HEATER