APPENDIX G (cont)
OPTIONS1: Options Configuration
OPTIONS2: Options Configuration
DESCRIPTION STATUS DEFAULT POINT
Cooler Fluid 1=Water
2=Med.Brine
3 = Low Brine
1FLUIDTYP
Min. Load Valve Select No/Yes No MLV_FLG
Head Press. Control Type 0 = None
1=AirCooled
2=WaterCooled
3 = Common Condenser
4 = Independent Condenser
0 HEAD_TYP
Var Head Pressure Select 0 = None
1=4-20mA
2=0-20mA
3=20-0mA
0 VHPTYPE
Pressure Transducers No/Yes Yes PRESS_TY
Cooler Pump Control Off/On Off CPC
Condenser Pump Interlock Off/On Off CND_LOCK
Condenser Pump Control 0 = Not Controlled
1 = On when STATE is On
2 = On when compressors are On
0 CNPC
Condenser Fluid Sensors No/Yes No CD_TEMP
EMM Module Installed No/Yes No EMM_BRD
DESCRIPTION STATUS DEFAULT UNITS POINT
Control Method 0 = Switch
1=7daysched.
2 = Occupancy
3 = CCN
0 CONTROL
Loading Sequence Select 1 = Equal loading
2 = Staged loading
1 SEQ_TYPE
Lead/Lag Sequence Select 1 = Automatic
2 = Circuit A leads
3 = Circuit B leads
1 LEAD_TYP
Compressor Sequence 1 = Automatic
2 = Compressor 1 Leads
3 = Compressor 2 Leads
1 COMP_SEQ
Cooling Setpoint Select 0=Single
1 = Dual, remote switch controlled
2 = Dual, 7 day clock controlled
3 = Dual, CCN occupancy controlled
4 = 4-20 mA input
0 CLSP_TYP
Heating Setpoint Select 0=Single
1 = Dual, remote switch controlled
2 = Dual, 7 day clock controlled
3 = Dual, CCN occupancy controlled
4 = 4-20 mA input
0HTSP_TYP
Ramp Load Select Enable/Disable Enable RAMP_EBL
Heat Cool Select Cool Cool HEATCOOL
High LCW Alert Limit 2to60 60.0 ∆FLCW_LMT
Minutes off time 0to15 0 min DELAY
Deadband Multiplier 1.0to4.0 2.0 Z_GAIN
Close Control Select Disable/Enable Disable CLS_CTRL
Ice Mode Enable Disable/Enable Disable ICE_CNFG
Current Unbalance SetPnt 10 to 25 10 % CUR_TRIP
Enable Noflow Detection Disable/Enable Enable NOFLOWEN
Winterize Alert Config Disable/Enable Enable WINTMSC
Alarm Relay Usage 0=AlertsandAlarms
1=AlarmsOnly
2 = Off
0 ALRMCNFG