Table 12 Configuration Mode and Sub-Mode Directory (cont)
SUB
MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
SLCT CLSP X COOLING SETPOINT SELECT Default: Single
Single
Dual Switch
Dual 7 day
Dual CCN Occupied
4 to 20 mA Input (requires EMM)
HTSP X HEATING SETPOINT SELECT Default: Single
Single
Dual Switch
Dual 7 day
Dual CCN Occupied
4 to 20 mA Input (requires EMM)
RL.S ENBL/DSBL RAMP LOAD SELECT Default: Enable
CRMP X.X COOLING RAMP LOADING Default: 1.0
Range: 0.2 to 2.0
HRMP X.X HEATING RAMP LOADING Default: 1.0
Range: 0.2 to 2.0
HCSW COOL/HEAT HEAT COOL SELECT Default: Cool
Z.GN X.X DEADBAND MULTIPLIER Default: 2.0
Range: 1.0 to 4.0
BRN.L YES/NO HXC BRINE CONFIG LOCK Default: No
Yes,ifbrineFIOPisinstalled(liquidline
solenoid valves).
SERV H.PGN XX.X HEAD PRESSURE P GAIN Default: 1.0
Range: –20 to 20
H.IGN XX.X HEAD PRESSURE I GAIN Default: 0.1
Range: –20 to 20
H.DGN XX.X HEAD PRESSURE D GAIN Default: 0.0
Range: –20 to 20
H.MIN XXX.X WATER VALVE MINIMUM POS. Default: 20%
Range: 0 to 100%
MT.SP XXX.X °F MOTOR TEMP SETPOINT Default: 200 F (170 F for Brine)
BR.FZ XXX.X °F BRINE FREEZE POINT Default: 34 F
Range: 20 to 34 F
MC.SP XXX.X °F MAX. COND. TEMP SETPOINT Default: 152 F (GXN,R)
145 F (HXA)
118 F (HXC)
Range: 100 F To Default
EX.S.A XX.X % EXVA START POSITION Default: 20 %
Range: 0 T0 40 %
EX.S.B XX.X % EXVB START POSITION Default: 20 %
Range: 0 To 40 %
EN.A1 ENBL/DSBL ENABLE COMPRESSOR A1 Default: Enable (All)
EN.A2 ENBL/DSBL ENABLE COMPRESSOR A2 Disable (HX076-186, GXN,R080-178)
Enable (HX206-271, GXN,R204-350)
EN.B1 ENBL/DSBL ENABLE COMPRESSOR B1 Default: Enable (All)
EN.B2 ENBL/DSBL ENABLE COMPRESSOR B2 Disable (HX076-271, GXN,R080-268
Enable (GXN,R281-350)
W.DNE YES/NO WINTERIZATION PERFORMED
ECON YES/NO ECONOMIZED No (30HX076-146, 30GXN,R080-106,114)
Yes (30HX161-271,30GXN,R108,118-350)
EVPS X NUMBER OF EVAP. PASSES Range: 1 To 4
LWTC A/B CIRCUIT WITH LWT SENSOR According to number of cooler passes.
AP.SP XXX.X °F APPROACH SETPOINT
Default: 3.0 F
Range: 0.1 to 20.0 F
BCST TD.B.C ON/OFF CCN TIME/DATE BROADCAST Default: Off
OAT.B ON/OFF CCN OAT BROADCAST Default: Off
GS.BC ON/OFF GLOBAL SCHEDULE BROADCAST Default: Off
BC.AK ON/OFF BROADCAST ACKNOWLEDGER Default: Off
ENTER
ENTER
ENTER