25
Table 13 — Service Test Mode and Sub-Mode Directory
SUB-
MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
TEST ON/OFF SERVICE TEST MODE To Enable Service Test Mode, move Enable/Off/
Remote Contact switch to OFF. Change TEST to
ON. Move switch to ENABLE.
OUTS
EXV.A XXX % EXV % OPEN
VH.PA XXX % VAR HEAD PRESS %
OL.P.A ON/OFF OIL PUMP
MC.A1 ON/OFF MOTOR COOLING SOLENOID A1
MC.A2 ON/OFF MOTOR COOLING SOLENOID A2
OS.A1 ON/OFF OIL SOLENOID A1
OS.A2 ON/OFF OIL SOLENOID A2
EXV.B XXX % EXV % OPEN
VH.PB XXX % VAR HEAD PRESS %
OL.P.B ON/OFF OIL PUMP
MC.B1 ON/OFF MOTOR COOLING SOLENOID B1
MC.B2 ON/OFF MOTOR COOLING SOLENOID B2
OS.B1 ON/OFF OIL SOLENOID B1
OS.B2 ON/OFF OIL SOLENOID B2
FAN1 ON/OFF FAN 1 RELAY
Fans 1, 2 (080-150,160)
Fans 2, 4 (208, 228, 253, 268)
Fans 5, 6 (249, 264)
Fans 9, 10 (153, 163-178, 204,225,281-350)
Fans 15, 16 (253, 268)
FAN2 ON/OFF FAN 2 RELAY
Fans 3, 4 (080-178, 204, 225, 249, 264, 281-350)
Fan 3 (208, 228, 253, 268)
FAN3 ON/OFF FAN 3 RELAY
Fans 5, 6 (083, 093-160, 174, 204, 225)
Fans 6, 8 (253, 268)
Fans 7, 8 (118, 128, 138, 150, 160)
Fans 9, 10 (249, 264)
Fans 11, 12 (163, 178, 208, 228-268)
Fans 13, 14 (208, 228, 253, 268-350)
Fans 15, 16 (281-350)
FAN4 ON/OFF FAN 4 RELAY
Fans 5, 7 (208, 228, 253, 268)
Fans 5, 6, 7, 8 (281-350)
Fans 11, 12 (163, 178)
CLR.P ON/OFF COOLER PUMP RELAY
CLR.H ON/OFF COOLER HEATER
CND.P ON/OFF CONDENSER PUMP RELAY
RMT.A ON/OFF REMOTE ALARM RELAY
COMP
CC.A1 ON/OFF COMPRESSOR A1 RELAY
CC.A2 ON/OFF COMPRESSOR A2 RELAY
LD.A1 ON/OFF LOADER A1 RELAY
LD.A2 ON/OFF LOADER A2 RELAY
MLV ON/OFF MINIMUM LOAD VALVE Energizes circuit A and B solenoids
OL.H.A ON/OFF OIL HEATER
CC.B1 ON/OFF COMPRESSOR B1 RELAY
CC.B2 ON/OFF COMPRESSOR B2 RELAY
LD.B1 ON/OFF LOADER B1 RELAY
LD.B2 ON/OFF LOADER B2 RELAY
OL.H.B ON/OFF OIL HEATER
ENTER
ENTER
ENTER