Carrier ComfortVu TB-24-HM - Page 31

Carrier ComfortVu TB-24-HM
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
12
13
14
15
16
SW3
SW1
Config. 20:
2-Pipe,
1/2/3 Speeds
fan
Fan high
Fan medium
(or Economizer )
Fan low
Heat element
(2
nd
stage heat)
Cool/Heat valve
X
Config. 21:
2-Pipe, 1/2/3
Speeds fan
Cool/Heat PID
X
Cooll/Heat
valve PID
Config. 22:
2-Pipe,
Fan VFS
Cool/Heat valve
Fan VFS
Config. 23:
2-Pipe,
Fan VFS,
Cool/Heat PID
Cooll/Heat
valve PID
Fan VFS
Fan high
Fan medium
(or Economizer )
Fan low
X
Economizer
(option – SW1.6 ON)
X
X
X
Heat element
(2
nd
stage heat)
Heat element
(2
nd
stage heat)
Heat element
(2
nd
stage heat)
87654321
654321
87654321
654321
87654321
654321
87654321
654321
JP3
JP2
3
Jumpers
JP2, JP3
for analog
outputs
1
3 1
JP3
JP2
3 1
3 1
JP3
JP2
3 1
3 1
JP3
JP2
3 1
3 1
- 31 -
Wiring and DIP switch/jumper configurations – FC systems – 2-pipe
Outputs
Fan VFS, PID valves: 0-10 Vdc, 0.5 mA Not isolated
Control – Fan on/off, Heat elements, Cool/Heat valves, Economizer: 24 Vac, 0.5A max
See drawing on page 21 for DIP switch and jumper locations.
(2)
(1)
(1)
(5)
(5)
Economizer
(option – SW1.6 ON)
(5)
(2) (2)
(5)
(3)
(3)
(3)
(3)
(1)
SW3.1, SW3.2 – Fan speeds: 1 speed (Low): SW3.1 = ON, SW3.2 = OFF
2 speeds(Low and High): SW3.1 = OFF, SW3.2 = ON
3 speeds(Low, Medium, and High): SW3.1 = OFF, SW3.2 = OFF
(2)
SW3.4 – 2
nd
heating stage: ON = Enable, OFF = Disable
(3)
SW3.5 – Chilled beam option: ON = Enable chilled beam (fan will not run with cooling)
(5)
SW1.6 – Terminal 12 operation: ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (1/2 speeds/VFS)
Important: Economizer will not work in 3 fan speeds configuration.