- 5 -
Sensing Element: Range Accuracy
Temperature 41° F to 95° F (5° C to 35° C) ±1.0° F (0.5° C)
Humidity 10% to 90 % ±3.0% typical
Motion Sensing:
Sensor Type PIR, quad, omnidirectional
Distance 16.4 feet (5m)
Detection range (HxV) 90° x 30°
Movement speed 2.62 to 3.94 ft/s (0.8 to 1.2 m/s)
Detection object: 15.75 x 9.84 in. (400 x 250 mm)
Power 24 Vac, ±10%, 50-60Hz, 4VA
NOTE Devices connected to outputs, such as a fan, will increase VA requirements.
Communication BACnet MS/TP with baud rates up to 76.8 kbps, detected and set automatically by the
BACnet Thermostat. Max 127 devices.
Inputs T1, 0 – Normally open or normally closed dry contract, or
0-10 Vdc analog input, or
50 kOhm thermistor @ 25°C
A, B - Communication +/- (RS485)
IN1, 0 - Normally open or Normally closed dry contract, or
0-10 Vdc analog input, or
50 kOhm thermistor @ 25°C
C, R - Power: 24 Vac
Outputs 11, 12, 13 – Digital outputs, 3A max.
14 – Digital outputs 0.3A max
. 15 and 16 – Depends on application.
Digital output 0.3A max., or
Analog output 0-10 Vdc, 5 mA max., not isolated
Environmental Operating Range 50° to 122°F (10° to 50°C), 10 to 90% relative humidity, non-condensing
Mounting • If using an electrical box, mount the included wallplate to a standard 4" x 2" electrical
box using the two larger mounting screws, then mount the thermostat to
the wallplate using the three smaller mounting screws.
If not using an electrical box, flush-mount thermostat to wall (no wallplate needed).