EasyManua.ls Logo

Carrier ComfortVu TB-24-HM - Page 36

Carrier ComfortVu TB-24-HM
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
12
13
14
15
16
SW3
SW1
Config. 39:
4-Pipe,
1/2/3 Speeds fan ,
Heat valve PID,
Cool valve PID
Fan high
Fan medium
(or Economizer )
Fan low
Heat element
(2
nd
stage heat)
Cool valve PID
Heat valve PID
87654321
654321
JP3
JP2
3
Jumpers
JP2, JP3
for analog
outputs
1
3 1
- 36 -
Wiring and DIP switch/jumper configurations – FC systems – 4-pipe
Outputs
See drawing on page 21 for DIP switch and jumper locations.
PID valves: 0-10 Vdc, 0.5 mA Not isolated
Control – Fan on/off, Heat elements, Cool/Heat valves, Economizer: 24 Vac, 0.5A max
(1)
SW3.1, SW3.2 – Fan speeds: 1 speed (Low): SW3.1 = ON, SW3.2 = OFF
2 speeds(Low and High): SW3.1 = OFF, SW3.2 = ON
3 speeds(Low, Medium, and High): SW3.1 = OFF, SW3.2 = OFF
(2)
SW3.4 – 2
nd
heating stage: ON = Enable, OFF = Disable
(3)
SW3.5 – Chilled beam option: ON = Enable chilled beam (fan will not run with cooling)
(5)
SW1.6 – Terminal 12 operation: ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (1/2 speeds)
Important: Economizer will not work in 3 fan speeds configuration.
(1)
(5)
(2)
(3)

Related product manuals