P52 – Cool valve proportional band (FC Only!)
Range: 2...10°C / 4...20°F
Default: 2°C / 4°F
P53 – Cool proportional low limit (FC Only!)
Range: 0...100%
Default: 0%
Cool prop.
low limit
P54 – Cool proportional high limit (FC Only!)
Range: 0...100%
Default: 100%
Cool prop.
high limit
P55 – Heat valve proportional band (FC Only!)
Range: 2...10°C / 4...20°F
Default: 2°C / 4°F
P56 – Heat proportional low limit (FC Only!)
Range: 0...100%
Default: 0%
Heat prop.
low limit
P57 – Heat proportional high limit (FC Only!)
Range: 0...100%
Default: 100%
Heat prop.
high limit
Cool valve proportional band
(°F)(°C)
Cool valve proportional band
(°F)(°C)
0-10V Valve opening from fully closed to fully open.
Minimum valve opening.
Maximum valve opening.
0-10V Valve opening from fully closed to fully open.
Minimum valve opening.
Maximum valve opening.
- 51 -
Technician Settings (cont.)