Menu Structure
Table 9 illustrates the complete hierarchy of menus and parame-
ters for the EconoMi$er X system.
The Menus in display order are:
•STATUS
SETPOINTS
SYSTEM SETUP
ADVANCED SETUP
•CHECKOUT
•ALARMS
NOTES:
1. For 2 speed unit, under SYSTEM SETUP: EQUIPMENT= CONV,
AUX2 I = W, and FAN TYPE = 2 SPEED.
2. More sophisticated controller setups, including for DCV or power
exhaust, are available by referring to Table 11 options.
3. Fan speed options are:
1) 1 Speed
2) 2 Speed
3) 2 Speed: 1 Heat, 1 Cool.
4) 3 Speed: 1 Heat, 2 Cool.
4. Do not use 3 speed setting for LC units.
IMPORTANT: Table 9 illustrates the complete hierarchy. Menu
parameters may be different depending on configuration. For
example, none of the DCV parameters appear for a system that
does not have a DCV (CO
2
) sensor.
IMPORTANT: The default setting on the W7220 controller is
for a “Fan Type” with 2 speed, which is correct for 2 speed
units. For a 1 (single) speed unit, the setting under SYSTEM
SETUP > FAN TYPE must be changed to 1 speed.
Table 8 — Standard W7220 Controller Configuration
CONTROLLER
MENU ITEM
FOR SINGLE SPEED UNIT FOR 2-SPEED UNIT
NOTE
DEFAULT SET TO: DEFAULT SET TO:
SET POINTS
MAT SET 53°F 38°F to 70°F 53°F 38°F to 70°F
LOW T LOCK 32°F –45°F to 80°F 32°F –45°F to 80°F
DRYBLB SET 63°F 48°F to 80°F 63°F 48°F to 80°F Only displayed if using single DB OA sensor
ENTH CURVE ES3 ES1 to ES5 ES3 ES1 to ES5 Only displayed if using a single enthalpy OA sensor
MIN POS 4.4 vdc 2 to 10 vdc N/A N/A Only displayed if set up for single speed unit
MIN POS H n/a n/a 4.4 vdc 2 to 10 vdc Only displayed if set up for 2 speed unit
MIN POS L n/a n/a 6.0 vdc 2 to 10 vdc Only displayed if set up for 2 speed unit
SYSTEM SETUP
INSTALL 1/1/2010 Current date 1/1/2010 Current date
EQUIPMENT CONV CONV CONV CONV Always set to CONV, even on HP units
AUX2 IN W W W W Always set to W
FAN TYPE 2-speed 1-speed 2-speed 2 -speed See Note 3
AUX1 OUT NONE SYS NONE SYS Set to SYS for remote FDD monitoring
OCC INPUT INPUT INPUT INPUT Always set to INPUT
LEGEND
N/A Not applicable
DCV Demand Controlled Ventilation
db —Dry Bulb
O/A Outdoor Air
HP —Heat Pump
FDD Fault Detection and Diagnostic
LC Liquid Crystal