Point Check Function
Press the remote control’s LED display or LED or MUTE three times, and then press AIR DIRECTION or SWING three times in ten
seconds: the buzzer rings for two seconds. The unit enters the information enquiry status. Press the LED DISPLAY or AIR DIRECTION to
check the next or previous item’s information.
When the unit enters the information enquiry status, it displays the code name in 2 seconds (see Table 6).
Table 6 — Information Enquiry
When the unit enters the information enquiry status, the code value appears for 25 seconds (see Table 7).
Table 7 — Information Enquiry
ENQUIRY INFORMATION DISPLAYING CODE MEANING
T1
T1
T1 temp. Indoor
T2
T2
T2 temp. Evaporator coil
T3
T3
T3 temp. Outdoor coil
T4
T4
T4 temp. Outdoor air
TS
TS
Set Temperature
TP
TP
TP temp. Comp disc
Td
TH
Control Target Temperature
Compressor Target Frequency
FT
Targeted Frequency
Compressor Actual Frequency
Fr
Actual Frequency
Indoor Fan Speed
IF
Indoor fan speed
Outdoor Fan Speed
OF
Outdoor fan speed
EXV Opening Angle
LA
EXV opening angle
Compressor continuous running time
CT
Compressor continuous running time
Compressor stop causes
ST
Compressor stop causes
Reserve
A0
Reserve
A1
Reserve
b0
Reserve
b1
Reserve
b2
Reserve
b3
Reserve
b4
Reserve
b5
Reserve
b6
Reserve
dL
Reserve
Ac
Reserve
Uo
Reserve
Td
ENQUIRY INFORMATION DISPLAY VALUE MEANING REMARK
T1,T2,T3,T4,
T2B,TP,TH,
Tar get ed
Frequency,
Actual
Frequency
-1F,-1E,-1d,-1c,-1b,-1A -25,-24,-23,-22,-21,-20
1. The displaying temperature is the actual
value.
2. The temperature is °C no matter what kind
of remote control is used.
3. T1,T2,T3,T4,T2B display range:-25~70,
TP display range:-20~130.
4. Frequency display range: 0~159HZ.
5. If the actual value exceeds the range, it
displays the maximum value or minimum
value.
-19—99 -19—99
A0,A1,…A9 100,101,…109
b0,b1,…b9 110,111,…119
c0,c1,…c9 120,121,…129
d0,d1,…d9 130,131,…139
E0,E1,…E9 140,141,…149
F0,F1,…F9 150,151,…159
Indoor fan speed
/Outdoor fan speed
0OFF
1,2,3,4
Low speed, Medium speed, High speed,
Turbo
For some big capacity motors
14-FF
Actual fan speed = Display value turns to
decimal value and then multiply by 10. The
unit is RPM.
For some small capacity motors, the display
value is from 14-F (hexadecimal), the
corresponding fan speed range is from 200-
2550 RPM.
EXV opening angle 0-FF
Actual EXV opening value = Display value
turns to decimal value and then multiply by 2.
Compressor continuous
running time
0-FF 0-255 minutes
If the actual value exceeds the range, it
displays the maximum value or minimum
value.
Compressor stop causes 0-99
For a detailed meaning, please consult with
an engineer.
Decimal display
Reserve 0-FF