F. Dehumidify and Super Dehumidify Capabilities
This model fan coil is capable of responding to a signal from indoor system control (Thermidistat, zoning control) to operate in comfort control
modes such as Super Dehumidify Mode. Consult literature provided with indoor system control to determine if these operating modes are available,
and to see control set up instructions. No special setup or wiring of fan coil is required.
PROCEDURE 10FV4B FAN COIL SEQUENCE OF OPERATION
The FV4B will supply airflow in a range which is more than twice the range of a standard fan coil. It is designed to provide nominal cooling
capacities at a 50°F evaporator temperature and the required airflow which enables it to match with 4 air conditioner or heat pump system sizes.
Table 2 outlines the CFM range for the different FV4B Fan Coil sizes.
A. Continuous Fan
Thermostat closes circuit R to G.
The blower runs at continuous fan airflow.
B. Cooling Mode - Single speed
If indoor temperature is above temperature set point and humidity is below humidity set point, thermostat closes circuits R to G, R to Y/Y2
andRtoO.
The fan coil delivers single speed cooling airflow.
C. Cooling Mode - Dehumidification
If indoor temperature is above temperature set point and humidity is above humidity set point, thermostat or Thermidistat closes circuits R
to G, R to O, and R to Y/Y2, and humidistat or Thermidistat opens R to DH.
The fan coil delivers airflow which is approximately 80 percent of the nominal cooling airflow to increase the latent capacity of the system.
D. Cooling Mode - Super Dehumidify Operation (See Fig. 22 for Quick Reference Guide)
NOTE: The indoor control used, such as Thermidistat, must be capable of providing Super Dehumidify operation mode and control must be
configured as outlined in its installation instructions. Consult indoor control literature to determine if control is capable of providing Super
Dehumidify inputs and for configuration instructions.
If the indoor temperature is below the temperature set point and the humidity is above the humidity set point, the Thermidistat closes circuit R
to O, opens circuits R to DH and R to G, and cycles circuit R to Y/Y2 (for single speed system R to Y1, or R to Y1 and Y/Y2 for 2-speed system).
The ECM motor reads the G signal to the fan coil while the heat pump is operating, (circuit R to Y/Y2 for single speed system, R to Y1 or R to
Y1 and Y/Y2 for 2-speed system), closed (24 vac). If circuit R to G is closed (24 vac), the motor will deliver airflow at the full cooling or cooling
plus dehumidify mode requested value. If circuit R to G is open (0 vac) for super dehumidify mode, the motor delivers reduced airflow to maximize
the humidity removal of the system while minimizing overcooling.
E. Electric Heat Heating Mode
Thermostat closes circuit R to W/W1, or W2.
The fan coil delivers the selected electric heat airflow.
F. Heat Pump Heating Mode - Single speed
Thermostat closes circuits R to G and R to Y/Y2.
The fan coil delivers single speed heat pump heating airflow.
G. Heat Pump Heating with Auxiliary Electric Heat
Thermostat closes circuits R to G, R to Y/Y2 and/or R to Y1 with R to W/W1 or W2 (and R to O in the case of defrost).
In the event that electric heating is called for by the thermostat while the heat pump is also operating in either heating or defrost modes, the motor
will modify its airflow output, if necessary, to provide an airflow which is defined as safe for the operation of the electric heater during heat pump
operation. That airflow is the greater of the heat pump heating airflow and the electric heater only airflow.
PROCEDURE 11TROUBLESHOOTING ECM MOTOR AND CONTROLS
CAUTION: High voltage is always present at motor. Disconnect power to unit before removing or replacing
connectors or servicing motor. Wait at least 5 min after disconnecting power before opening motor. Failure to follow this
CAUTION could result in minor personal injury or product and property damage.
Fig. 20Humidistat Wiring for De-Humidify Mode
A95316
EASY SELECT
BOARD TERMINAL
BLOCK
D
H
J1
R
HUMIDISTAT
REMOVE
JUMPER
15