EasyManua.ls Logo

Carrier FV4B - CFM Range for FV4 B Units; FV4 B Fan Coil Airflow Delivery (CFM) in Cooling Mode; FV4 B Fan Coil Airflow Delivery (CFM) in Heat Pump Only Heating Mode

Carrier FV4B
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The ECM motor used with this product contains two parts: the control module and motor winding section. Do not assume the motor or module
is defective if it will not start. Go through the steps described below before replacing control module, Easy Select Board or entire motor. The
control module is available as a replacement part.
Table 2CFM Range for FV4B Units
FAN COIL SIZE SYSTEM SIZES CFM RANGE
FV4BNF002 024, 030, 036 450-1275
FV4BNF003 024, 030, 036, 042 525-1475
FV4BNF005 036, 042, 048 550-1700
FV4BNB006 042, 048, 060 550-2150
Table 3FV4B Fan Coil Airflow Delivery (CFM) in Cooling Mode
UNIT
SIZE
OUTDOOR
UNIT
CAPACITY
OPERATING MODE
FAN ONLY
LO/MED/HI
Single-Speed
Application
Two-Speed
Application
High Speed Low Speed
Nominal
A/C
Cooling
A/C
Cooling
Dehumidity
Nominal
A/C
Cooling
A/C
Cooling
Dehumidity
Nominal
A/C
Cooling
A/C
Cooling
Dehumidity
002
018
024
030
036
525
700
875
1050
420
560
700
840
735
1100
590
880
440
660
350
530
350/350/525
350/440/700
440/550/875
525/660/1050
003
024
030
036
042
700
875
1050
1225
560
700
840
980
735
1100
590
880
440
660
415
530
415/440/700
440/550/875
525/660/1050
610/770/1225
005
030
036
042
048
875
1050
1225
1400
700
840
980
1120
1100
1470
880
1175
660
880
530
705
440/550/875
525/660/1050
610/770/1225
700/880/1400
006
036
042
048
060
1050
1225
1400
1750
840
980
1120
1400
1100
1470
1835
880
1175
1470
660
880
1100
530
705
880
525/660/1050
610/770/1225
700/880/1400
875/1100/1750
NOTE
1. The above airflows result with the AC/HP CFM ADJUST select jumper set on NOM.
2. Airflow can be adjusted +15 percent or -10 percent by selecting HI or LO respectively for all modes except fan only.
3. Dry coil at 230 volts and with 10kw heater and filter installed.
4. Airflows shown are at standard air conditions.
Table 4FV4B Fan Coil Airflow Delivery (CFM) in Heat Pump Only Heating Mode
UNIT
SIZE
OUTDOOR
UNIT
CAPACITY
OPERATING MODE
FAN ONLY
LO/MED/HI
Single-Speed
Application
Two-Speed
Application
High Speed Low Speed
Heat Pump
Comfort
Heat Pump
Efficiency
Heat Pump
Comfort
Heat Pump
Efficiency
Heat Pump
Comfort
Heat Pump
Efficiency
002
018
024
030
036
420
560
700
840
525
700
875
1050
660
990
735
1100
395
595
440
660
350/350/470
350/395/630
440/520/785
525/595/945
003
024
030
036
042
560
700
840
980
700
875
1050
1225
660
990
735
1100
415
595
440
660
415/415/630
440/520/785
525/595/945
610/695/1100
005
030
036
042
048
700
840
980
1120
875
1050
1225
1400
990
1320
1100
1470
595
795
660
880
440/520/785
525/595/945
610/695/1100
700/795/1260
006
036
042
048
060
840
980
1120
1400
1050
1225
1400
1750
990
1325
1655
1100
1470
1835
595
795
990
660
880
1100
525/595/945
610/695/1100
700/795/1260
875/990/1575
NOTE
1. The above airflows result with the AC/HP CFM ADJUST select jumper set on NOM.
2. Airflow can be adjusted +15 percent or -10 percent by selecting HI or LO respectively for all modes except fan only.
3. Dry coil at 230 volts and with 10kw heater and filter installed.
4. Airflows shown are at standard air conditions.
16

Table of Contents

Related product manuals