The Room Controller 2 Location 
The CRC2 can be installed on a unit only if this unit is the 
Fancoil Cabinet.
For wall-mounting, follow the instructions below:
If fitted to a wall, the Room Controller must be mounted:
•Inthesameareawheretheunitislocated,preferablyonan
inside partitioning wall.
•Approximately1.5mfromoor.
•Onasectionofwallwithoutpipesorductwork
General information
IMPORTANT:
Read the entire instruction manual before starting the 
installation.
• Fortrouble-freeinstallation,whichshouldbecarriedoutbya
qualified installer, follow the installation chart sequence.
• Followallcurrentnationalsafetycoderequirements.
  In particular ensure that a properly sized and connected 
ground wire is in place.
• Afterinstallationthoroughlytestthesystemoperationand
explain all system functions to the owner.
• Leavethismanualwiththeownerforconsultationduringfuture
periodic maintenance.
• Disposeofpackagingmaterialinaccordancewithlocal
requirements.
• Themanufacturerdeniesanyresponsibilityandwarrantyshall
be void if these installation instructions are not observed.
• Inspectequipmentfordamageduetoimpropertransportation
or handling: file an immediate claim with the shipping company.
  Do not install or use damaged units.
• Incaseofanymalfunctioningturntheunitoff,disconnectthe
mains power supply and contact a qualified service engineer.
 
Room Controller 2: Hydronic Fancoil Solutions
Power
Note that the Room Controller 2 requires no batteries and is not 
“power stealing”.  It requires 12 VDC to be connected for proper 
operation, which is easily obtained from the Unit connected to it. 
The Room Controller 2 will not operate without this connection.
If the indoor air sensor on the Room Controller has been 
selected, it should NOT be mounted:
•Closetoawindow,onanoutsidewall,ornexttoadoorleadingto
the outside.
•Exposedtodirectlightandheatfromalamp,sun,replace,or
other temperature-radiating object which may cause a false 
reading.
•Closetoorindirectairowofaheatingorcoolingsupply.
•Inareaswithpooraircirculation,suchasbehindadoororinan
alcove.
• Maximumcablelength:150m