SETUP=FANCOIL:
HPiAC AIRFLOW:
COMFORT (default)
EFFICIENCY
MAXIMUM
Selects the airflow of the fan coil when heating or cooling with a
heat pump (or cooling with an AC unit). COMFORT is a
decreased airflow used to improve humidity control. EFFI-
CIENCY is the airflow used to meet specified ratings. MAXI-
MIM is a fixed airflow speed of 400 CFMiton based on the
outdoor unit size.
DEHUM AIRFLOW:
NORMAL (default)
HIGH
Normal airflow adjustment used during dehumidifying. If duct
sweating is an issue, selecting HIGH will increase the dehumidi-
fying airflow speed and reduce the sweating.
HEATER SIZE:
(choices dependent upon fan coil model)
This will show the heater size entered during the start-up process.
This value can be changed to another value (limited by the model
of the tim coil). If the electric heater is self-identifying, this value
is not shown.
SETUP = HEAT PIMP / AC:
COOLING LOCKOUT:
NONE (default)
45° F.
50° F.
55° F.
Outside temperature below which cooling will not be provided.
ENTERED SIZE:
(dependent on indoor unit model)
Size of the outdoor unit entered during the start-up process. If the
outdoor unit is a communicating model, this value will not be
shown. This size can be changed here but is limited to sizes that the
indoor unit can handle.
DEFROST INTERVAL:
30 minutes
60 minutes
90 minutes (defimlt)
120 minutes
Time interval at which defrost cycles can occur on a heat pump.
ELECT HEAT LOCKOUT:
NONE (default)
+5 to 55 deg. F
Outside temperature above which the electric heat will not operate.
HIGH COOL LATCH:
NONE (default)
80- ll0degF
Outside temperature above which only the high speed (of a
2-speed outdoor unit) will run when cooling.
SETUP = ACCESSORIES
FILTER TYPE:
MEDIA
EAC
MEDIA+EAC
CLEAN INTERVAL: 30 to 180 days (of blower operation).
(Default 90)
Interval at which the Clean Filter notification will turn on. Applies
to EAC or MEDIA+EAC filter selection only.
SETUP = HI MIDIFIER
HUMIDIFIER INSTALLED:
NO
YES
If YES, indicates to the system whether a humidifier is installed
and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months of humidifier
operation (default 6 months)
Interval at which the Change Humidify Pad notification will be
displayed.
HUMIDIFY WITH FAN:
NO (default)
YES
If YES, the humidifier will run with Continuous Fan if there is a
humidify demand.
SETUP = VENTILATOR
NOTE: Only appears if ventilator is installed.
CLEAN INTERVAL:
60 to i80 days of operation (default 90)
Interval at which the Clean Ventilator Pre-filter notification will
turn on.
SETUP = UV LIGHTS
UV LIGHTS INSTALLED:
NO
YES
If YES, indicates to the system whether UV lights are installed.
CHANGE INTERVAL:
6 to 48 months operation time (default 12 months)
Interval at which the Change UV Lights notification will be
displayed.
SETUP = SYSTEM MAINTENANCE
REMIND OWNER OF ROUTINE MAINTENANCE EVERY:
This setup is used to adjust the timer interval in which the normal
System Maintenance notification is turned on for the homeowner.
Range OFF, 6 to 24 months, (default 12)