11 62-12119
14. Remove or Open Exterior Panels.
15. Leak Checking.
a. Examine the unit for traces of oil residue. Leak check the unit
using an electronic leak detector. Leaks are typically found as
a dirty / oily residue near the leak location. All mechanical
joints to be leak tested can be found in the Appendix. Repair
as required and clean the unit using low pressure water.
16. Corrosion.
Perform on-going corrosion maintenance if corrosion found on
any painted surface. Perform these steps:
a. Remove loose corrosion material.
b. Lightly scuff up the surface with a Scotch-Brite Heavy Duty
Scour Pad (or similar).
c. Wipe down with isopropyl alcohol to remove loose material
and any grease.
d. Paint using the following standard paint specifications (pur-
chase locally).
17. Access Panels. Refer to Figure 11.
a. Remove the left and right hand evaporator access panels.
b. Check that the access panel seals are present and in good
condition to provide a good seal.
c. Check for excessive shaft end play on the evaporator motor.
d. Replace panels on completion assuring all hardware (includ-
ing the Mylar washer) is installed.
e. When reinstalling the panels, use a torque setting of 60 +5 in-
lbs. (6.8 N-M) and the pattern shown in Figure 11.
Figure 11 Access Panels
Part Color Brand Paint
Compressor /
Flash Tank
Grey DNT V-TOP #188
Frame White Cloud Rust-Oleum 9100 System