62-11848 6-2
A07
Evaporator  Fan  Motor  (EFM)
high amp draw
Verify motor rotates freely / no obstructions --
Replace motor --
A09
Defrost Valve (HGV) high amp
draw
Current draw  of  coil  high  or low  (approx. 1.33
amp)
Replace coil 5.10.1
A11
Main  Heat  Valve  (HGS2)  high
amp draw
Current  draw  of  coil  high  or  low  (approx.  1.6
amp)
Replace coil 5.10.1
A12 High temperature alarm
Box temperature is higher than  setpoint for 15
minutes.
A13 Low temperature alarm
Box  temperature  is  lower  than  setpoint  for  15
minutes.
A14 Defrost time > 45 minutes
Unit  has  been  in  defrost  for  more  than  45
minutes.
Verify defrost cycle operation
A15
Setpoint adjusted out of the 
range -20.2 to 86°F (-29°C to 
+30°C).
Check setpoint value entered. 3.5
EE
Evaporator  Temperature  Sen-
sor Failure
Return air sensor is defective. Replace
bAt Low Battery Voltage
Vehicle battery voltage low Correct
Check alternator system --
SE Maintenance needed. Perform unit basic maintenance
Table 6–2 Mechanical Indications
INDICATION / TROUBLE POSSIBLE CAUSES
REFERENCE 
SECTION
6.2 REFRIGERATION
6.2.1 Unit Will Not Cool
Compressor malfunction
Compressor drive (clutch) defective
Replace
Compressor defective
Refrigeration system
Defrost cycle has not terminated 6.2.5
Abnormal pressure 6.2.6
Hot gas solenoid malfunction 5.10
6.2.2 Unit Runs But Has Insufficient Cooling
Compressor Compressor defective Replace
Refrigeration system
Abnormal pressure 6.2.6
Expansion valve malfunction 6.2.10
Non-existent or restricted evaporator airflow 6.2.9
Table 6–1 Alarm Indications
ALARM Description CORRECTIVE ACTION