PG92MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
40
A13110
Table 15 – Deductions from Maximum Equivalent Vent Length - Ft. (M)
1. Use only the smallest diameter pipe possible for venting. Over-sizing may cause flame disturbance or excessive vent terminal icing or freeze-up.
2. NA - Not allowed.   Pressure switch will not close, or flame disturbance may result.
3. Vent sizing for Canadian installations over 4500 ft. (1370 M) above sea level are subject to acceptance by the local authorities having jurisdiction.
4. Size both the combustion air and vent pipe independently, then use the larger size for both pipes.
5. Assume the two 45_ elbows equal one 90_ elbow. Wide radius elbows are desirable and may be required in some cases.
6. Elbow and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
7. The minimum pipe length is 5 ft. (2 M) linear feet (meters) for all applications.
8. Use 3-in. (76 mm) diameter vent termination kit for installations requiring 4-in. (102 mm) diameter pipe.
9. A running Tee in the Combustion Air Pipe adds 0 ft. to the TEVL of the vent length.
Combustion Air and Vent Piping Insulation 
Guidelines
NOTE: Use closed cell, neoprene insulation or equivalent. 
The  vent  pipe  may  pass  through  unconditioned  areas.  The  amount  of
exposed pipe allowed is shown in Table 16.
1. Using  winter  design  temperature  (used  in  load  calculations),  find
appropriate temperature for your application and furnace model.
2. Determine the amount of total and exposed vent pipe.
3. Determine required insulation thickness for exposed pipe length(s).
4. When  combustion  air  inlet  piping is  installed  above  a  suspended
ceiling,  the  pipe  MUST  be  insulated  with  moisture  resistant
insulation such as Armaflex or other equivalent type of insulation.
5. Insulate  combustion  air  inlet  piping  when  run  in  warm,  humid
spaces.
6. Install the insulation per  the insulation manufacturer’s installation
instructions.
NOTE: Pipe length (ft. / M) specified for maximum pipe lengths located
in  unconditioned  spaces  cannot  exceed  total  allowable  pipe  length  as
calculated from Table 14.
Configure the Furnace
Near Furnace Vent Connections
Offsets in the vertical portion of the vent pipe should be made with 45
deg. elbows instead of 90 deg. elbows. Short horizontal runs of vent pipe
are difficult to pitch correctly and may trap water in the vent pipe.
Trapped water  in the  vent pipe  may result in nuisance pressure switch
tripping.
Install the Vent and Combustion Air Pipes
With the furnace installed in the required position, remove the  desired
knockouts from the casing. It will be necessary to remove one knockout
for  the  vent  pipe  and  the  other  knockout  for  the  combustion  air
connection. See Fig. 15.
Use a flat blade screwdriver and tap on the knockout on opposite sides,
where the knockout meets the casing. Fold the knockout down with duct
pliers  and work the  knockout back  and  forth  until it is  removed. Trim
any excess metal from the knockout with tin snips.
The vent elbow can be rotated to the required location on the casing if
necessary. See Fig. 53. To rotate the vent elbow:
Pipe Diameter (in): 1-1/2 2 2-1/2 3 4
Mitered 90º Elbow
8 (2.4) 8 (2.4) 8 (2.4) 8 (2.4) 8 (2.4)
Medium Radius 90º Elbow
5 (1.5) 5 (1.5) 5 (1.5) 5 (1.5) 5 (1.5)
Long Radius 90º Elbow
3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9)
Mitered 45º Elbow
4 (1.2) 4 (1.2) 4 (1.2) 4 (1.2) 4 (1.2)
Medium Radius 45º Elbow
2.5 (0.8) 2.5 (0.8) 2.5 (0.8) 2.5 (0.8) 2.5 (0.8)
Long Radius 45º Elbow
1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5)
Tee
16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9)
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death. 
To route the vent pipe and combustion air pipe through the furnace, the
manufacturer  supplied  kit  must  be  used.  Failure  to  properly  seal  the
blower  compartment  from  the  furnace  vestibule  could  result  in  the
circulation of carbon monoxide throughout the structure. The vent pipe
and  combustion  air  pipe  must  be  a  continuous  pipe  while  passing
through  the  blower  compartment.  Seals  supplied  in  this  kit  must  be
installed per the instructions provided. Follow all  procedures outlined
in these instructions.