PG92MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
44
Installing the Vent Pipe Adapter and Combustion Air 
Pipe Adapter
NOTE: The rubber coupling that attaches to the vent pipe adapter must
be used. The  adapter seals the  vent  pipe to the  casing and  reduces the
strain on the vent elbow attached to the inducer.
1. Apply  the  gaskets  to  the  vent  pipe  and  combustion  air  pipe
adapters. If supplied, remove and discard round center “slug” from
interior of gasket. See Fig. 58.
A13074
Fig. 58 – Vent Coupling and Adapter with Gaskets
NOTE: The vent pipe adapter can be distinguished from the inlet pipe
adapter by the absence of an internal pipe-stopping ring. The vent pipe
can pass through the vent pipe adapter; it cannot pass through the inlet
pipe adapter.
2. Align  the  screw  holes  in  the  plastic  vent  pipe  adapter  with  the
dimples in the casing.
3. Pilot drill the screw holes for the adapter in  the casing and attach
the vent pipe adapter to the furnace with sheet metal screws
4. Slide the end of the rubber vent coupling with notches in it over the
standoffs on the vent pipe adapter.
5. Insert a length of vent pipe through the coupling into the outlet of
the vent elbow.
6. Tighten the clamp around the outlet of the vent elbow. Torque the
clamp to 15 lb-in.
Install the remaining vent and combustion air pipes as shown below. It is
recommended that all pipes be cut, prepared, and pre-assembled before
permanently cementing any joint.
1. Working from furnace to outside, cut pipe to required length(s).
2. De-burr inside and outside of pipe.
3. Chamfer outside edge of pipe for better distribution of primer and
cement.
4. Clean and dry all surfaces to be joined.
5. Check dry fit of pipe and mark insertion depth on pipe.
6. Insert the vent pipe into the vent elbow.
7. Torque clamp on vent elbow 15 lb-in.
8. Torque clamp on vent coupling 15 lb-in.
9. Insert the combustion air pipe into the adapter. 
10. Pilot drill a screw hole through the adapter into the combustion air
pipe and secure the pipe to the adapter with sheet metal screws. DO
NOT DRILL INTO POLYPROPYLENE VENT PIPES. Use an
optional accessory vent coupling, if needed.
11. Seal  around  the  combustion  air  pipe  with  silicone  or  foil  tape.
SILICONE  SEALERS  MAY  NOT  BE  APPROPRIATE  FOR
POLYPROPYLENE  VENT  SYSTEMS.  SEE
POLYPROPYLENE  VENT  SYSTEM  MANUFACTURER’S
INSTRUCTIONS.
12. After pipes have been cut and pre-assembled, apply generous layer
of cement primer to pipe fitting socket and end of pipe to insertion
mark.  Quickly  apply  approved  cement  to  end  of  pipe  and  fitting
socket  (over  primer). Apply  cement  in  a  light,  uniform  coat  on
inside of socket to prevent buildup of excess cement. Apply second
coat. DO NOT CEMENT POLYPROPYLENE FITTINGS.
13. While cement is still wet, twist pipe into socket with 1/4-in. turn.
Be sure pipe is fully inserted into fitting socket.
14. Wipe excess cement from joint. A continuous bead of cement will
be visible around perimeter of a properly made joint.
15. Handle pipe joints carefully until cement sets.
16. Horizontal  portions  of  the  venting  system  shall  be  supported  to
prevent  sagging.  Space  combustion  air  piping  and  vent  piping
hangars as shown in Table 17. Support pipes using perforated metal
hanging strap or commercially available hangars or straps designed
to support plastic pipe.
Winter 
Design 
Temp 
°C
Unit Size
120,000 BTUH
140,000 BTUH
Uninsulated  3/8-in. Insulation 1/2-in. Insulation Uninsulated  3/8-in. Insulation 1/2-in. Insulation
Pipe Dia. 
mm
64  76 102 64  76 102 64  76 102 64  76 102 64 76 102 64 76 102
-7 3.0 15.2 12.2 3.0 22.9 28.9 3.0 22.9 32.0 1.5 16.7 15.2 1.5 19.8 32.0 1.5 19.8 38.1
-18 3.0 6.1 4.6 3.0 16.8 13.7 3.0 19.8 15.2 1.5 7.6 4.6 1.5 19.8 15.2 1.5 19.8 18.3
-29 3.0 3.0
3.0 10.7 7.6 3.0 13.7 9.1 1.5 3.0 1.5 1.5 13.7 9.1 1.5 15.2 12.2
-40 3.0 1.5
3.0 7.6 4.6 3.0 9.1 6.1 1.5 1.5 1.5 9.1 6.1 1.5 35 7.6
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
DO  NOT  use  cement to join  polypropylene  venting systems. Follow
the  polypropylene  venting  system  manufacturer’s  instructions  for
installing polypropylene venting systems.
CAUTION
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death. 
To route the vent pipe and combustion air pipe through the furnace, the
manufacturer  supplied  kit  must  be  used.  Failure  to  properly  seal  the
blower  compartment  from  the  furnace  vestibule  could  result  in  the
circulation of carbon monoxide throughout the structure. The vent pipe
and  combustion  air  pipe  must  be  a  continuous  pipe  while  passing
through  the  blower  compartment.  Seals  supplied  in  this  kit  must  be
installed per the instructions provided. Follow all procedures outlined
in these instructions.
Attach gaskets to vent pipe and
combustion air adapters.
Vent Coupling and Adapter
NOTICE
!
The  following  instructions  are for  PVC/ABS  DWV  vent piping  only.
DO  NOT  USE  THESE  TECHNIQUES  FOR  POLYPROPYLENE
VENT  PIPING  SYSTEMS.  See  the  polypropylene  vent  system
manufacturer’s  instructions  for  installing  polypropylene  venting
systems.