PG92MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
56
Heating value = 1050 Btu/cu ft.
Specific gravity = 0.62
Therefore: Orifice No. 44
Manifold pressure: 3.4-in. w.c. (847 Pa)
(Furnace  is  shipped  with  No.  44  orifices.  In  this  example,  all  main
burner  orifices  are  the  correct  size  and  do  not  need  to  be  changed  to
obtain proper input rate.)
NOTE: To convert gas manifold Table pressures to Pascals, multiply the
in. w.c. value by 249.1 Pa/in. w.c. (1 in. w.c. = 249.1 Pa).
Check Inlet Gas Pressure
The  inlet  gas  pressure  must  be  checked  with  the  furnace  operating  in
maximum  heat.  This  is  necessary  to  make  sure  the  inlet  gas  pressure
does not fall below the minimum pressure of 4.5 in. w.c.
1. Make  sure  the  gas  supply  is  turned  off  to  the  furnace  and  at  the
electric switch on the gas valve.
2. Loosen set screw on inlet tower pressure tap no more than one full
turn  with  a  3/32-in.  hex  wrench  or  remove  the  1/8-in.  NPT  plug
from the inlet pressure tap on the gas valve.
3. Connect a manometer to the inlet pressure tap on gas valve.
4. Turn on furnace power supply.
5. Turn gas supply manual shutoff valve to ON position.
6. Turn furnace gas valve switch to ON position.
7. Jumper  R  and  W  thermostat  connections  at  the  furnace  control
board.
8. When main burners ignite, confirm inlet gas pressure is between 4.5
in. w.c. (1125 Pa) and 13.6 in. w.c. (3388 Pa).
9. Remove jumper across thermostat connections to terminate call for
heat. Wait until the blower-OFF delay is completed.
10. Turn furnace gas valve electric switch to OFF position.
11. Turn gas supply manual shutoff valve to OFF position.
12. Turn off furnace power supply.
13. Remove manometer from the inlet pressure tap of the gas valve.
14. Tighten  set  screw  on  inlet  tower  pressure  tap  with  3/32-in.  hex
wrench,  or  if  1/8-in.  NPT  plug  was  removed,  apply  pipe  dope
sparingly to end of plug and re-install in the gas valve.
Adjust Manifold Pressure
1. Adjust  manifold  pressure  to  obtain  proper  gas  input  rate.  See
Fig. 65.
a. Refer to the correct manifold pressure table for the appropriate 
model.
b. Turn gas valve ON/OFF switch to OFF.
c. Loosen set screw on manifold tower pressure tap no more than 
one full turn with a 3/32-in. hex wrench, or remove the 1/8 inch 
NPT plug from the manifold pressure tap on the gas valve.
d. Connect a water column manometer or similar device to 
manifold pressure tap.
e. Turn gas valve ON/OFF switch to ON.
f. Manually close blower door switch.
g. Jumper R and W thermostat connections on control to start 
furnace. See Fig. 38.
h. Remove regulator adjustment cap from gas valve pressure 
regulator and turn adjusting screw (3/16 or smaller flat-tipped 
screwdriver) counterclockwise (out) to decrease input rate or 
clockwise (in) to increase input rate. See Fig. 65.
i. When correct input is obtained, replace cap that conceals gas 
valve regulator adjustment screws. Main burner flame should be 
clear blue, almost transparent See Fig. 66.
A170140
Fig. 65 – Gas Valve with Tower Pressure Ports
A11461
Fig. 66 – Burner Flame
j. Remove jumper R to W. 
2.  Verify natural gas input rate by clocking meter. 
NOTE: Contact your  HVAC distributor or gas supplier for  metric gas
meter Tables, if required.
a. Turn off all other gas appliances and pilots served by the meter.
b. Jumper R to W.
c. Run furnace for 3 minutes.
d. Measure time (in sec) for gas meter to complete one revolution 
and note reading. The 2 or 5 cubic feet dial provides a more 
accurate measurement of gas flow.
e. Refer to Table 24 for cubic ft. of gas per hr.
WARNING
!
FIRE HAZARD
Failure  to  follow  this  warning  could  result  in  personal  injury,  death,
and/or property damage. 
Inlet  pressure  tap  set  screw  must  be  tightened  and  1/8-in.  NPT  pipe
plug must be installed to prevent gas leaks.
NOTICE
!
DO NOT set manifold pressure less than 2.8-in. w.c. (697 Pa) or more
than 3.8 in. w.c. (947 Pa) for natural gas. If required manifold pressure
is  outside this  range,  change  main  burner  orifices  to  obtain  manifold
pressure in this range.
Burner Flame
Burner
Manifold