PG92MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
L12F012
Fig. 6 – Air for Combustion, Ventilation, and Dilution for Outdoors
L12F013
Fig. 7 – Air for Combustion, Ventilation, and Dilution from Indoors
3. ONE OUTDOOR OPENING requires:
a. 1 sq. in. (645 sq. mm) of free area per 3,000 BTUh (734 
mm2/kW) for combined input of all gas appliances in the space 
per Fig. 6 and Table 4.
b. Not less than the sum of the areas of all vent connectors in the 
space.
The  opening  shall  commence  within  12  in.  (300  mm)  of  the  ceiling.
Appliances in the space shall have clearances of at least 1 in. (25 mm)
from the sides and back and 6 in. (150 mm) from the front. The opening
shall  directly  communicate  with  the  outdoors  or  shall  communicate
through a vertical or horizontal duct to the outdoors or spaces (crawl or
attic) that freely communicate with the outdoors. 
Indoor Combustion Air NFPA & AGA 
Standard and Known-Air-Infiltration Rate Methods 
Indoor  air is  permitted for  combustion, ventilation, and dilution,  if the
Standard or Known-Air-Infiltration Method is used. 
Standard Method
1. The space has no less volume than 50 cubic feet per 1,000 BTUh of
the  maximum  input ratings  for  all  gas  appliances  installed  in  the
space and
2. The air infiltration rate is not known to be less than 0.40 air changes
per hour (ACH). 
The Known Air Infiltration Rate Method shall be used, if the infiltration
rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH 
Infiltration rates greater than 0.60 ACH shall not be used. The minimum
required volume of the space varies with the number of ACH and shall
be determined per Table 5 or Equations 1 and 2. Determine the minimum
required  volume  for  each  appliance  in  the  space  and  add  the  volumes
together to get the total minimum required volume for the space. 
Table 5  -  Minimum  Space  Volumes  were  determined  by  using  the
following  equations from the current  edition  of  the National  Fuel  Gas
Code ANSI Z223.1/NFPA 54, 9.3.2.2:
1. For  other  than  fan-assisted  appliances,  such  as  a  draft
hood-equipped water heater:
A04002
2. For fan-assisted appliances such as this furnace:
A04003
If: 
I
other = combined input of all  other  than fan-assisted appliances  in
BTUh/hr 
I
fan = combined input of all fan-assisted appliances in BTUh/hr 
ACH = air changes per hour (ACH shall not exceed 0.60.)
The  following  requirements  apply  to  the  Standard  Method  and  to  the
Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closeable doors between rooms. 
b. Combining spaces on same floor level. Each opening shall have 
free area of at least 1 in.2/1,000 BTUh (2,000 mm2/kW) of the 
total input rating of all gas appliances in the space, but not less 
than 100 in.2 (0.06 m2). One opening shall commence within 12 
in. (300 mm) of the ceiling and the second opening shall 
commence within 12 in. (300 mm) of the floor. The minimum 
dimension of air openings shall be at least 3 in. (80 mm). See 
Fig. 7.
c. Combining space on different floor levels. The volumes of 
spaces on different floor levels shall be considered as 
 0 LQLPXPRSHQLQJVL]HLVVTLQVTPPZLWK
PLQLPXPGLPHQVLRQVRI‐LQPP
0LQLPXPRI‐LQPPZKHQW\SH‐%YHQWLVXVHG
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Many  homes  require  air  to  be  supplied  from  outdoors  for  furnace
combustion, ventilation, and dilution of flue gases. 
The  furnace  combustion  air  supply  must  be  provided  in  accordance
with this instruction manual. 
Volume
Other
=
21ft
3
ACH
I 
other
1000 Btu/hr
Volume
Fan
=
15ft
3
ACH
I 
fan
1000 Btu/hr