Fig. 19 – Furnace Pitch Requirements
Supply Air Connections 
For a furnace not equipped with a cooling coil, the outlet duct shall be
provided  with  a  removable  access  panel.  This  opening  shall  be
accessible when the furnace is installed and shall be of such a size that
the  heat  exchanger  can  be  viewed  for  possible  openings  using  light
assistance or a  probe  can  be  inserted for sampling  the  air stream. The
cover attachment shall prevent leaks. 
Connect  supply-air  duct  to  flanges  on  furnace  supply-air  outlet.  Bend
flange upward to 90°° with wide duct pliers. See Fig. 20. The supply-air
duct  must  be  connected  to  ONLY  the  furnace  supply-outlet-air  duct
flanges or air conditioning coil casing (when used). DO NOT cut main
furnace  casing  side  to  attach  supply  air  duct,  humidifier,  or  other
accessories. All  supply-side  accessories  MUST  be  connected  to  duct
external to furnace main casing. 
A10493
Fig. 20 – Duct Flanges
Return Air Connections 
The return-air duct can only be connected to bottom of the furnace. sides 
(left or right), or a combination of bottom and side(s) of main furnace
casing. Bypass humidifier may be attached into unused return air
side of the furnace casing. See Fig. 22, Fig. 23, and Fig. 24.
Bottom Return Air Inlet 
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel, see Fig. 24.
A11036
Fig. 21 – Upflow Return Air Configurations and Restrictions
A11037
Fig. 22 – Downflow Return Air Configurations
and Restrictions
A13109
Fig. 23 – Horizontal Return Air Configurations
 and Restrictions
WARNING
!
FIRE HAZARD
A failure to follow this warning could cause personal injury, death 
and/or property damage.
Never connect return-air ducts to the back of the furnace. Follow 
instructions below. 
UPFLOW DOWNFLOW HORIZONTAL
YES
NO
NO
YES
YES
YES
NO
120°
MIN
YES
120°
MIN
YES
120°
MIN
90°
90°
PERFORATED
DISCHARGE DUCT
FLANGE
HORIZONTAL  
RETURN NOT 
PERMITTED FOR  
ANY MODEL
APPLIES TO ALL MODEL SIZES