PG92MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
39
3. For  each  pipe,  multiply  the  number  of  elbows  by  the  equivalent
length for the type of elbow used. Record the equivalent length of
all the elbows for each pipe.
4. If  a  Tee  is  used  on  the  termination  (Alberta  and  Saskatchewan,
when required) record the equivalent length of the Tee used.
5. Calculate Total  Equivalent Vent  Length  by  adding  the  equivalent
lengths  of  the  fittings  to  the  lengths  of  the  individual  vent  and
combustion air pipes.
A170122A
Fig. 51 – Recommended Combustion Air Inlet Moisture Trap
6. When  using  polypropylene  venting  systems  with  flexible  vent
pipes, perform adjustments for the equivalent length of the flexible
vent pipe to  the calculated total equivalent venting system length.
See the polypropylene vent system manufacturer’s instructions for
details.
7. Select  a  diameter  of  vent  pipe  from  Table 14  and  note  the
Maximum  Equivalent  Vent  Length  (MEVL)  shown  for  that
application for that specific furnace input size. Compare the Total
Equivalent Vent Length (TEVL) to the MEVL:
8. If the Total Equivalent Vent Length is shorter  than the Maximum
Equivalent Vent Length for the diameter of pipe chosen, then that
diameter of pipe selected may be used.
9. If  the Total Vent  Length  is longer  than  the  Maximum  Equivalent
Vent  Length  for  the  diameter  of  pipe  chosen,  that  diameter  pipe
MAY  NOT  be  used  for  venting  the  furnace.  Try  the  next  larger
diameter pipe
.
NOTE:  If  the  calculated  Total  Equivalent  Vent  Lengths  results  in
different diameter pipes for the vent and combustion air, select the larger
diameter for both pipes.
NOTE: If the Maximum Vent Length for diameter of the pipe selected is
longer  than  the  measured  length  and  the  equivalent  length  of  all  the
fittings  and  terminations  (TEVL),  recalculate  Total  Equivalent  Vent
Length  using  the  next  smaller  diameter.  If  the  Maximum  Equivalent
Vent  Length  is  still  longer  than  the  longer  TEVL  of  the  vent  pipe  or
combustion air pipe, then that diameter of pipe selected may be used.
When installing vent systems pipe lengths of 10 ft. (3 M) or less, use the
smallest allowable pipe diameter. Using a pipe size greater than required
for  short  venting  systems  may  result  in  loss  of  efficiency,  incomplete
combustion, flame disturbance, or flame sense lockout.
For vent systems longer than 10 ft. (3 M), any larger diameter vent pipe
shown in Table 14 FOR THAT SIZE FURNACE may be used.
Table 14 – Maximum Equivalent Vent Length
NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows. Use Table 15 -
Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
1. Inducer Outlet Restrictor disk (P/N 337683-401; 1.25-in. (32 mm) Dia.) shipped in the loose parts bag or available through Replacement Components required under 10-ft. (3 M) TEVL in
all orientations. Required for installations from 0 - 2000 (0 to 610 M) above sea level. Failure to use an outlet restrictor may result in flame disturbances or flame sense lock-out. 
2. Inducer Outlet Restrictor disk (P/N 337683-401; 1.25-in. (32 mm) Dia.) available through Replacement Components required for no greater than 5-ft. (1.5 M) TEVL in downflow and
horizontal orientations only. Required for installations from 0 - 2000 (0 to 610 M) above sea level.
3. Inducer Outlet Restrictor disk (P/N 337683-401; 1.50-in. (38 mm) Dia.) available through Replacement Components required for no greater than 5-ft. (1.5 M) TEVL in downflow and
horizontal orientations only. Required for installations from 0 - 2000 (0 to 610 M) above sea level.
Single Stage 92% - Ft.
Unit Size 
40,000 
1
60,000 
2
80,000
100,000 
3
120,000 
3
Altitude 
(feet)
Pipe Dia. (in) 1 ½ 2 2 ½ 1 ½ 2 2 ½ 3 1 ½ 2 2 ½  3 4 2 2 ½ 3 4 2 ½ 3 4
0-2000 20 85 185
20
100 175 200 15 55 130 175 200 20 80 175 200
10
75 185
2001-3000
15
80 175 95 165 185
10
49
125 165 185
15 75
165 185 70 175
3001-4000
70
160 16 90 155 175 115 155 175
155
175 5 65 165
4001-4500
10
155
15
85
150
170
44 110
150 165
10
70 170
N/A
60
160
4501-5000 145 80 165 145 160
65
150 165
5001-6000 60 130 75 140 155 41 100 135 150 140 155 155
6001-7000
5
55 120 13 70 130 145
N/A
38
90
125 140 60 135 145 50 140
7001-8000 50 110 10 65 120 135 36 120 125
N/A
55 125 135 46 130
8001-9000
N/A
30 95 5 60 115 125 33 80 110 115 50 115 125 43 120
9001-10000 25 85 N/A 55 105 115 30 75 100 105 45 100 115 39 115
Single Stage 92% - Meters
Unit Size 
40,000 
1
60,000 
2
80,000
100,000 
3
120,000 
3
Altitude 
(meters)
Pipe Dia. (mm) 38 51 64 38 5 64 76 38 51 64 76 102 51 64 76 102 64 76 102
0-610 6.0 25.9 56.3
6.0
30.4 53.3 60.9 4.5 16.7 39.6 53.3 60.9 6.0 24.3 53.3 60.9
3.0
22.8 56.3
611-914
4.5
24.3 53.3 28.9 50.2 56.3
3.0
14.9
38.1 50.2 56.3
4.5
22.8 50.2 56.3 21.3 53.3
915-1219
21.3
48.7 4.8 27.4 47.2 53.3 35.0 47.2 53.3 0.0
47.2
53.3 1.5 19.8 50.2
1220-1370
3.0
47.2
4.5
25.9
45.7
51.8
13.4
33.5 45.7 50.2
3.0
21.3 51.8
N/A
18.2
48.7
1371-1524 44.1 24.3 50.2 0.0 44.1 48.7 19.8 45.7 50.2
1525-1829 18.2 39.6 22.8 42.6 47.2 12.4 30.4 41.1 45.7 0.0 42.6 47.2 47.2
1830-2134
1.5
16.7 36.5 3.9 21.3 39.6 44.1
N/A
11.5 27.4 .1 42.6 18.2 41.1 44.1 15.2 42.6
2135-2438 15.2 33.5 3.0 19.8 36.5 41.1 10.9 0.0 36.5 38.1
N/A
16.7 38.1 41.1 14.0 39.6
2439-2743
N/A
9.1 28.9 1.5 18.2 35.0 38.1 10.0 24.3 33.5 35.0 15.2 35.0 38.1 13.1 36.5
2744-3048 7.6 25.9 N/A 16.7 32.0 35.0 9.1 22.8 30.4 32.0 13.7 30.4 35.0 11.8 35.0