Dual Vacuum Pump Connections
in deep vacuum. (Refer to
charging line from cylinder to receiver outlet (king)
valve. Purge charging line at outlet valve.
Note weight of refrigerant cylinder.
Open liquid valve on refrigerant cylinder. Open king
been added as indicated by scales. Correct charge
will be found in Table 2-1.
It is possible that all liquid may not be pulled into the
receiver, as outlined in step d. In this case, vapor
When refrigerant cylinder weight (scale) indicates
that the correct charge has been add
line valve on cylinder and backseat the king valve.
Start unit in cooling mode. Run approximately ten
minutes. Partially block off air flow to condenser coil so
discharge pressure rises to 14.8 kg/cm
sight glass is full and no refrigerant is in the upper