Table 28 — VFD Unit Parameters – 48LC**14 (cont)
TERMINAL 53
LOW VOLTAGE
TERMINAL 53
HIGH VOLTAGE
TERMINAL 53
LOW REFERENCE
TERMINAL 53
HIGH REFERENCE
RESET
MODE
AUTO. RESTART
TIME (s)
RFI
FILTER
Motor
Option
Voltage 6–10 6–11 6–14 6–15 14–20 14–21 14–50
STD
208/230 2 [10] 0 [60] [3] 600 [0]
460 2 [10] 0 [60] [3] 600 [0]
575 2 [10] 0 [60] [3] 600 [0]
MID
208/230 2 [10] 0 [60] [3] 600 [0]
460 2 [10] 0 [60] [3] 600 [0]
575 2 [10] 0 [60] [3] 600 [0]
HIGH
208/230 2 [10] 0 [60] [3] 600 [0]
460 2 [10] 0 [60] [3] 600 [0]
575 2 [10] 0 [60] [3] 600 [0]
ULTRA
208/230 2 [10] 0 [60] [3] 600 [0]
460 2 [10] 0 [60] [3] 600 [0]
575 2 [10] 0 [60] [3] 600 [0]
Table 29 — VFD Unit Parameters – 48LC**17
REGIONAL
SETTINGS
GRID
TYPE
MOTOR
POWER
MOTOR
VOLTAGE
MOTOR
FREQUENCY
(Hz)
MOTOR
CURRENT
(MUST-HOLD
AMPS)
MOTOR
NOMINAL
SPEED (RPM)
Motor
Option
Voltage
Motor
P/N
VFD
Carrier P/N
VFD
Mfr P/N
0–03 0–06 1–20 1–22 1–23 1–24 1–25
STD
208/230 HD58FE654 HK30WA371 131L9796 [1] [102] [10] 230 60 9.2 1735
460 HD58FE654 HK30WA377 131L9864 [1] [122] [10] 460 60 4.2 1735
575 HD58FE577 HK30WA383 131N0227 [1] [132] [11] 575 60 4.9 1710
MID
208/230 HD60FK657 HK30WA373 131L9798 [1] [102] [14] 230 60 21.2 1760
460 HD60FK657 HK30WA380 131L9867 [1] [122] [14] 460 60 9.7 1760
575 HD60FL576 HK30WA384 131N0229 [1] [132] [14] 575 60 7.2 1745
HIGH
208/230 HD62FK654 HK30WA374 131L9799 [1] [102] [15] 230 60 28.0 1760
460 HD62FK654 HK30WA381 131L9868 [1] [122] [15] 460 60 13.7 1760
575 HD62FL576 HK30WA384 131N0229 [1] [132] [15] 575 60 8.9 1750
ULTRA
208/230 HD64FK654 HK30WA375 131L9800 [1] [102] [16] 230 60 37.3 1755
460 HD64FK654 HK30WA386 131L9869 [1] [122] [16] 460 60 16.9 1755
575 HD64FL576 HK30WA388 131N0233 [1] [132] [16] 575 60 12.6 1755
START
DELAY
(sec)
FLYING
START
MIN SPEED FOR
FUNCTION (Hz)
MOTOR
THERMAL
PROTECTION
PRESET REFERENCE
Motor
Option
Voltage 1–71 1–73 1–82 1–90 3–10 [0] 3–10 [1] 3–10 [2] 3–10 [3] 3–10 [4] 3–10 [5] 3–10 [6] 3–10 [7]
STD
208/230 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%
460 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%
575 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%
MID
208/230 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%
460 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%
575 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%
HIGH
208/230 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%
460 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%
575 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%
ULTRA
208/230 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%
460 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%
575 2.0 [1] 1.0 [4] 0% 56.64% 82.40% 100% 100% 0% 0% 0%