LEGEND
Table 2 — Humidi-MiZer Reheat Control Board I/O
POINT NAME TYPE
CONNECTION PIN
NUMBER
UNIT CONNECTION NOTE
Humidistat/LTLO DI, 24VAC J1A - 1 (1) LTLO
Thermostat W1 DI, 24VAC J1A - 2 (2) CTB - REHEAT - 4
Econ Y1 DI, 24VAC J1A - 6 (6) CTB - REHEAT - 5
Thermostat G DI, 24VAC J1B - 1 (7) CTB - REHEAT - 1
24V Power (J1) 24VAC J1B - 3 (9) CTB - R
24V Power (J2) 24 VAC J2 - 1 CTB - R
Econ Y2 DI, 24VAC J1B - 5 (11) CTB - REHEAT - 7 2 - circ only
COMP1 DO, 24VAC J1A - 5 (5) CTB - HEAT - 6
IFM DO, 24VAC J1B - 4 (8) CTB - REHEAT - 2
COMP2 DO, 24VAC J1B - 4 (10) CTB - REHEAT - 8
LSV DO, 24VAC J2 - 2 FTP (BLK)
DSV1 DO, 24VAC J2 - 3 DSV
NOT LSV DO, 24VAC J2 - 4 2 - circ only
DSV2 DO, 24VAC J2 - 5 2 - circ only
COMP Compressor
CTB Control Terminal Board
DI Discrete Input (switch)
DO Discrete Output (switch)
DSV Discharge (gas) Solenoid Valve
ECON Economizer
FPT Freeze Protection Thermostat
IFM Indoor (supply) Fan Motor
LSV Liquid Solenoid Valve
LTLO Low Temperature Lockout
REHEAT Connection Strip REHEAT (on CTB)
Table 3 — Inputs/Modes/Outputs Summary
INPUT
MODE
OUTPUT
Y1 Y2 W1 G
HUM/
LTLO
COMP
1
COMP
2
IFM LSV1 LSV2
LSV
NOT
DSV1 DSV2
OFF OFF OFF ON OFF Normal Fan OFF OFF ON=G OFF OFF ON=R OFF OFF
ON OFF OFF On OFF Normal Cool1 ON=Y1 OFF ON=G OFF OFF ON=R OFF OFF
ON ON OFF ON OFF Normal Cool2 ON=Y2 ON ON=G OFF OFF ON=R OFF OFF
OFF OFF ON X OFF Normal Heat 1 OFF OFF ON=G OFF OFF ON=R OFF OFF
OFF OFF OFF ON ON Reheat Dehumidify ON ON ON=G ON ON OFF ON=R ON=R
ON OFF OFF ON ON
Subcool Cir1/
Reheat Cir2
Cool1 and Cool2 /
Subcool-Dehumidify
ON ON ON=G ON ON OFF OFF ON=R
ON ON OFF ON ON
Subcool Cir1
and Cir2
Cool1 and Cool2 /
Subcool-Dehumidify
ON ON ON=G ON ON OFF OFF OFF
OFF OFF ON X ON Heat Override Heat 1 OFF OFF ON=G OFF OFF ON=R OFF OFF
OFF OFF
ON+
W2
X ON Heat Override Heat 1 and 2 OFF OFF ON=G OFF OFF ON=R OFF OFF