B.V.A VFD/ACTUATOR CONFIG
B.V.ABP.FS VFD/Act. Fire Speed/Pos. 0 to 100 % BLDGPFSO 100 83
B.V.ABP.MN VFD/Act. Min.Speed/Pos. 0 to 50 % BLDGPMIN 0 83
B.V.ABP.MX VFD Maximum Speed 50 to 100 % BLDGPMAX 100 83
B.V.ABP.1M BP 1 Actuator Max Pos. 85 to 100 % BP1SETMX 100 84
B.V.ABP.2M BP 2 Actuator Max Pos. 85 to 100 % BP2SETMX 100 84
B.V.ABP.CL BP Hi Cap VFD Clamp Val. 5 to 25 % BLDGCLMP 10 84
FAN.T FAN TRACKING CONFIG
FAN.TFT.CF Fan Track Learn Enable Yes/No DCFM_CFG No 84
FAN.TFT.TM Fan Track Learn Rate 5 to 60 min DCFMRATE 15 84
FAN.TFT.ST Fan Track Initial DCFM –20000 to 20000 CFM DCFMSTRT 2000 84
FAN.TFT.MX Fan Track Max Clamp 0 to 20000 CFM DCFM_MAX 4000 84
FAN.TFT.MN Fan Track Minimum Clamp –20000 to 0 CFM DCFM_MIN –1000 84
FAN.TFT.AD Fan Track Max Correction 0 to 20000 CFM DCFM_ADJ 1000 85
FAN.TFT.OF Fan Track Internl EEPROM –20000 to 20000 CFM DCFM_OFF 0 85
FAN.TFT.RM Fan Track Internal RAM –20000 to 20000 CFM DCFM_RAM 0 85
FAN.TFT.RS Fan Track Reset Internal Yes/No DCFMRSET No 85
FAN.TSCF.C Supply Air CFM Config 1 to 2 (multi-text strings) SCFM_CFG 1 85
B.PID BLDG.PRESS.PID CONFIGS
B.PIDBP.TM Bldg.Pres.PID Run Rate 5 to 120 sec BPIDRATE 10 85
B.PIDBP.P Bldg.Press. Prop. Gain 0 to 5 BLDGP_PG 0.5 85
B.PID
BP.I Bldg.Press. Integ. Gain 0 to 2 BLDGP_IG 0.5 85
B.PIDBP.D Bldg.Press. Deriv. Gain 0 to 5 BLDGP_DG 0.3 85
ACT.C BLDG.PRES. ACTUATOR CFGS
ACT.CBP.1 BLDG.PRES. ACT.1 CONFIGS
ACT.CBP.1SN.1 BP 1 Serial Number 1 0 to 9999 BP_1_SN1 0 84, 86
ACT.CBP.1SN.2 BP 1 Serial Number 2 0 to 6 BP_1_SN2 0 84, 86
ACT.CBP.1SN.3 BP 1 Serial Number 3 0 to 9999 BP_1_SN3 0 84, 86
ACT.CBP.1SN.4 BP 1 Serial Number 4 0 to 254 BP_1_SN4 0 84, 86
ACT.CBP.1C.A.LM BP1 Cntrl Angle Lo Limit 0 to 90 BP1_CALM 35 84, 86
ACT.CBP.2 BLDG.PRES. ACT.2 CONFIGS
ACT.CBP.2SN.1 BP 2 Serial Number 1 0 to 9999 BP_2_SN1 0 84, 86
ACT.CBP.2SN.2 BP 2 Serial Number 2 0 to 6 BP_2_SN2 0 84, 86
ACT.CBP.2SN.3 BP 2 Serial Number 3 0 to 9999 BP_2_SN3 0 84, 86
ACT.CBP.2SN.4 BP 2 Serial Number 4 0 to 254 BP_2_SN4 0 84, 86
ACT.CBP.2C.A.LM BP2 Cntrl Angle Lo Limit 0 to 90 BP2_CALM 35 84, 86
PG.EN Prognostics BP Enable Disable/Enable PG_BP_EN
PG.DB Prognostics BP Deadband 0 to 1 PG_BP_DB
D.LV.T COOL/HEAT SETPT. OFFSETS
L.H.ON
Dmd Level Lo Heat On –1 to 2 ^F DMDLHON 1.5 35, 54, 64
H.H.ON Dmd Level(+) Hi Heat On 0.5 to 20.0 ^F DMDHHON 0.5 54, 64
L.H.OF Dmd Level(–) Lo Heat Off 0.5 to 2.0 ^F DMDLHOFF 1 35, 54, 65
L.C.ON Dmd Level Lo Cool On –1 to 2 ^F DMDLCON 1.5 54, 64
H.C.ON Dmd Level(+) Hi Cool On 0.5 to 20.0 ^F DMDHCON 0.5 54, 64
L.C.OF Dmd Level(–) Lo Cool Off 0.5 to 2.0 ^F DMDLCOFF 1 54, 64
C.T.LV Cool Trend Demand Level 0.1 to 5.0 ^F CTRENDLV 0.1 54, 64
H.T.LV Heat Trend Demand Level 0.1 to 5.0 ^F HTRENDLV 0.1 54, 65
C.T.TM Cool Trend Time 30 to 600 sec CTRENDTM 120 54, 64
H.T.TM Heat Trend Time 30 to 600 sec HTRENDTM 120 54, 65
DMD.L DEMAND LIMIT CONFIG.
DM.L.S Demand Limit Select 0 to 3 (multi-text strings) DMD_CTRL 0 42, 47, 58
D.L.20 Demand Limit at 20 ma 0 to 100 % DMT20MA 100 42, 58
SH.NM Loadshed Group Number 0 to 99 SHED_NUM 0 58
SH.DL Loadshed Demand Delta 0 to 60 % SHED_DEL 0 58
SH.TM Maximum Loadshed Time 0 to 120 min SHED_TIM 60 58
D.L.S1 Demand Limit Sw.1 Setpt. 0 to 100 % DLSWSP1 80 42, 58
D.L.S2 Demand Limit Sw.2 Setpt. 0 to 100 % DLSWSP2 50 42, 58
IAQ INDOOR AIR QUALITY CFG.
DCV.C DCV ECONOMIZER SETPOINTS
DCV.CEC.MN Economizer Min.Position 0 to 100 % ECONOMIN 5 36, 42, 89, 90
DCV.CIAQ.M IAQ Demand Vent Min.Pos. 0 to 100 % IAQMINP 0 36, 42, 89, 90
DCV.CO.C.MX Economizer Min.Flow 0 to 20000 CFM OACFMMAX 2000 36, 42, 89
DCV.CO.C.MN IAQ Demand Vent Min.Flow 0 to 20000 CFM OACFMMIN 0 36, 42, 89
DCV.CO.C.DB Econ.Min.Flow Deadband 200 to 1000 CFM OACFM_DB 400 89
AQ.CF AIR QUALITY CONFIGS
AQ.CFIQ.A.C IAQ Analog Sensor Config 0 to 4 (multi-text strings) IAQANCFG 0 43, 88
AQ.CFIQ.A.F IAQ 4-20 ma Fan Config 0 to 2 (multi-text strings) IAQANFAN 0 43, 88-89
AQ.CFIQ.I.C IAQ Discrete Input Config 0 to 2 (multi-text strings) IAQINCFG 0 43, 47, 88-89
AQ.CFIQ.I.F IAQ Disc.In. Fan Config 0 to 2 (multi-text strings) IAQINFAN 0 43, 88-90
AQ.CFOQ.A.C OAQ 4-20ma Sensor Config 0 to 2 (multi-text strings) OAQANCFG 0 88
AQ.SP AIR QUALITY SETPOINTS
AQ.SPIQ.O.P IAQ Econo Override Pos. 0 to 100 % IAQOVPOS 100 43, 88-90
AQ.SPIQ.O.C IAQ Override Flow 0 to 31000 CFM IAQOVCFM 10000 88
AQ.SPDAQ.L Diff.Air Quality LoLimit 0 to 1000 DAQ_LOW 100 88-90
AQ.SPDAQ.H Diff. Air Quality HiLimit 100 to 2000 DAQ_HIGH 700 88-90
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
Table H — MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.