196
AQ.SPD.F.OF DAQ PPM Fan Off Setpoint 0 to 2000 DAQFNOFF 200 88-90
AQ.SPD.F.ON DAQ PPM Fan On Setpoint 0 to 2000 DAQFNON 400 88-90
AQ.SPIAQ.R Diff. AQ Responsiveness –5 to 5 IAQREACT 0 88-90
AQ.SPOAQ.L OAQ Lockout Value 0 to 2000 OAQLOCK 0 88-90
AQ.SPOAQ.U User Determined OAQ 0 to 5000 OAQ_USER 400 88-90
AQ.S.R AIR QUALITY SENSOR RANGE
AQ.S.RIQ.R.L IAQ Low Reference 0 to 5000 IAQREFL 0 88-90
AQ.S.RIQ.R.H IAQ High Reference 0 to 5000 IAQREFH 2000 88-90
AQ.S.ROQ.R.L OAQ Low Reference 0 to 5000 OAQREFL 0 88-90
AQ.S.ROQ.R.H OAQ High Reference 0 to 5000 OAQREFH 2000 88-90
IAQ.P IAQ PRE-OCCUPIED PURGE
IAQ.PIQ.PG IAQ Purge Yes/No IAQPURGE No 88-90
IAQ.PIQ.P.T IAQ Purge Duration 5 to 60 min IAQPTIME 15 88-90
IAQ.PIQ.P.L IAQ Purge LoTemp Min Pos 0 to 100 % IAQPLTMP 10 88-90
IAQ.PIQ.P.H IAQ Purge HiTemp Min Pos 0 to 100 % IAQPHTMP 35 88-90
IAQ.PIQ.L.O IAQ Purge OAT Lockout 35 to 70 dF IAQPNTLO 50 88-90
HUMD HUMIDITY CONFIGURATION
HM.CF Humidifier Control Cfg. 0 to 4 HUMD_CFG 0 91
HM.SP Humidifier Setpoint 0 to 100 % HUSP 40 91
H.PID HUMIDIFIER PID CONFIGS
H.PIDHM.TM Humidifier PID Run Rate 10 to 120 sec HUMDRATE 30 91
H.PIDHM.P Humidifier Prop. Gain 0 to 5 HUMID_PG 1 91
H.PIDHM.I
Humidifier Integral Gain 0 to 5 HUMID_IG 0.3 91
H.PIDHM.D Humidifier Deriv. Gain 0 to 5 HUMID_DG 0.3 91
ACT.C HUMIDIFIER ACTUATOR CFGS
ACTCSN.1 Humd Serial Number 1 0 to 9999 HUMD_SN1 0 92
ACTCSN.2 Humd Serial Number 2 0 to 6 HUMD_SN2 0 92
ACTCSN.3 Humd Serial Number 3 0 to 9999 HUMD_SN3 0 92
ACTCSN.4 Humd Serial Number 4 0 to 254 HUMD_SN4 0 92
ACTCC.A.LM Humd Ctrl Angle Lo Limit 0 to 90 HUMDCALM 85 92
DEHU DEHUMIDIFICATION CONFIG.
D.SEL Dehumidification Config 0 to 3(multi-text strings) DHSELECT 0 92
D.SEN Dehumidification Sensor 1 to 3(multi-text strings) DHSENSOR 1 92
D.EC.D Econ disable in DH mode? Yes/No DHECDISA Yes 92
D.V.CF Vent Reheat Setpt Select 0 to 1(multi-text strings) DHVHTCFG 0 92
D.V.RA Vent Reheat RAT offset 0 to 8 ^F DHVRAOFF 0 93
D.V.HT Vent Reheat Setpoint 55 to 95 dF DHVHT_SP 70 93
D.C.SP Dehumidify Cool Setpoint 40 to 55 dF DHCOOLSP 45 93
D.RH.S Dehumidify RH Setpoint 10 to 90 % DHRELHSP 55 93
HZ.RT Humidimizer Adjust Rate 5 to 120 HMZRRATE 30 94
HZ.PG Humidimizer Prop. Gain 0 to 10 HMZR_PG 0.8 94
DH.DB Dehumidify RH Deadband 1 to 30 % DHSENSDB 93
DH.TG Dehum Discrete Timeguard 10 to 90 DHDISCTG 93
CCN CCN CONFIGURATION
CCNA CCN Address 1 to 239 CCNADD 1 97
CCNB CCN Bus Number 0 to 239 CCNBUS 0 97
BAUD CCN Baud Rate 1 to 5 (multi-text strings) CCNBAUDD 3 97
BROD CCN BROADCST DEFINITIONS
BRODTM.DT CCN Time/Date Broadcast ON/OFF CCNBC On 97
BRODOAT.B CCN OAT Broadcast ON/OFF OATBC Off 97
BRODORH.B CCN OARH Broadcast ON/OFF OARHBC Off 97
BRODOAQ.B CCN OAQ Broadcast ON/OFF OAQBC Off 97
BRODG.S.B Global Schedule Broadcst ON/OFF GSBC Off 97
BRODB.ACK CCN Broadcast Ack'er ON/OFF CCNBCACK Off 97
SC.OV CCN SCHEDULES-OVERRIDES
SC.OVSCH.N Schedule Number 0 to 99 SCHEDNUM 1 35, 37, 97
SC.OVHOL.T Accept Global Holidays? YES/NO HOLIDAYT No 97
SC.OVO.T.L Override Time Limit 0 to 4 HRS OTL 1 97
SC.OVOV.EX Timed Override Hours 0 to 4 HRS OVR_EXT 0 97
SC.OVSPT.O SPT Override Enabled? YES/NO SPT_OVER Yes 97
SC.OVT58.O T58 Override Enabled? YES/NO T58_OVER Yes 97
SC.OVGL.OV Global Sched. Override? YES/NO GLBLOVER No 97
ALLM ALERT LIMIT CONFIG.
SP.L.O SPT lo alert limit/occ –10 to 245 dF SPLO 60 98
SP.H.O SPT hi alert limit/occ –10 to 245 dF SPHO 85 98
SP.L.U SPT lo alert limit/unocc –10 to 245 dF SPLU 45 98
SP.H.U SPT hi alert limit/unocc –10 to 245 dF SPHU 100 98
SA.L.O EDT lo alert limit/occ –40 to 245 dF SALO 40 98
SA.H.O EDT hi alert limit/occ –40 to 245 dF SAHO 100 98
SA.L.U EDT lo alert limit/unocc –40 to 245 dF SALU 40 98
SA.H.U EDT hi alert limit/unocc –40 to 245 dF SAHU 100 98
RA.L.O RAT lo alert limit/occ –40 to 245 dF RALO 60 98
RA.H.O RAT hi alert limit/occ –40 to 245 dF RAHO 90 98
RA.L.U RAT lo alert limit/unocc –40 to 245 dF RALU 40 98
RA.H.U RAT hi alert limit/unocc –40 to 245 dF RAHU 100 98
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
Table H — MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.