OAT.L OAT lo alert limit –40 to 245 dF OATL –40 98
OAT.H OAT hi alert limit –40 to 245 dF OATH 150 98
R.RH.L RARH low alert limit 0 to 100 % RRHL 0 98
R.RH.H RARH high alert limit 0 to 100 % RRHH 100 98
O.RH.L OARH low alert limit 0 to 100 % ORHL 0 98
O.RH.H OARH high alert limit 0 to 100 % ORHH 100 99
SP.L SP low alert limit 0 to 5 "H2O SPL 0 99
SP.H SP high alert limit 0 to 5 "H2O SPH 2 99
BP.L BP lo alert limit –0.25 to 0.25 "H2O BPL –0.25 99
BP.H BP high alert limit –0.25 to 0.25 "H2O BPH 0.25 99
IAQ.H IAQ high alert limit 0 to 5000 IAQH 1200 99
TRIM SENSOR TRIM CONFIG.
SAT.T Air Temp Lvg SF Trim –10 to 10 ^F SAT_TRIM 0 99
RAT.T RAT Trim –10 to 10 ^F RAT_TRIM 0 99
OAT.T OAT Trim –10 to 10 ^F OAT_TRIM 0 99
SPT.T SPT Trim –10 to 10 ^F SPT_TRIM 0 99
L.SW.T Limit Switch Trim –10 to 10 ^F LSW_TRIM 0 99
CCT.T Air Temp Lvg Evap Trim –10 to 10 ^F CCT_TRIM 0 99
DTA.1 A1 Discharge Temp Trim –10 to 10 ^F DTA1TRIM 0 99
SP.A.T Suct.Press.Circ.A Trim –50 to 50 PSIG SPA_TRIM 0 99
SP.B.T Suct.Press.Circ.B Trim –50 to 50 PSIG SPB_TRIM 0 100
DP.A.T Dis.Press.Circ.A Trim –50 to 50 PSIG DPA_TRIM 0 100
DP.B.T Dis.Press.Circ.B Trim –50 to 50 PSIG DPB_TRIM 0 100
SW.LG SWITCH LOGIC: NO / NC
FTS.L Filter Status Inpt-Clean Open/Close FLTSLOGC Open 100
IGC.L IGC Feedback - Off Open/Close GASFANLG Open 100
RMI.L RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open 100, 103
ENT.L Enthalpy Input - Low Open/Close ENTHLOGC Close 100
SFS.L Fan Status Sw. - Off Open/Close SFSLOGIC Open 100
DL1.L Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open 100
DL2.L Dmd.Lmt.Sw.2 - Off Open/Close DMD_SW2L Open 100
IAQ.L IAQ Disc.Input - Low Open/Close IAQINLOG Open 100
FSD.L Fire Shutdown - Off Open/Close FSDLOGIC Open 100
PRS.L Pressurization Sw. - Off Open/Close PRESLOGC Open 100
EVC.L Evacuation Sw. - Off Open/Close EVACLOGC Open 100
PRG.L Smoke Purge Sw. - Off Open/Close PURGLOGC Open 100
DH.LG Dehumidify Sw. - Off Open/Close DHDISCLG Open 100
DISP DISPLAY CONFIGURATION
TEST Test Display LEDs ON/OFF TEST Off 101
METR Metric Display ON/OFF DISPUNIT Off 101
LANG Language Selection 0 to 1 (multi-text strings) LANGUAGE 0 101
PAS.E Password Enable ENABLE/DISABLE PASS_EBL Enable 101
PASS Service Password 0000 to 9999 PASSWORD 1111 101
S.VFD SUPPLY FAN VFD CONFIG
N.VLT VFD1 Nominal Motor Volts 0 to 999 Volts VFD1NVLT 460
a
101
N.AMP VFD1 Nominal Motor Amps 0 to 999 Amps VFD1NAMP 55.0
a
101
N.FRQ VFD1 Nominal Motor Freq 10 to 500 Hz VFD1NFRQ 60 101
N.RPM VFD1 Nominal Motor rpm 50 to 30000 rpm VFD1Nrpm 1750 101
N.PWR VFD1 Nominal Motor HPwr 0 to 500 HP VFD1NPWR 40
a
101
M.DIR VFD1 Motor Direction 0=FWD, 1=REV VFD1MDIR 0 101
ACCL VFD1 Acceleration Time 0 to 1800 sec VFD1ACCL 30 101
DECL VFD1 Deceleration Time 0 to 1800 sec VFD1DECL 30 101
SW.FQ VFD1 Switching Frequency 0=1kHz, 1=4kHz, 2=8kHz, 3=12kHz VFD1SWFQ 2 101
TYPE VFD1 Type 0=LEN, 1=ANALOG VFD1TYPE 0 101
E.VFD EXHAUST FAN VFD CONFIG
N.VLT VFD2 Nominal Motor Volts 0 to 999 Volts VFD2NVLT 460
a
102
N.AMP VFD2 Nominal Motor Amps 0 to 999 Amps VFD2NAMP 28.7
a
102
N.FRQ VFD2 Nominal Motor Freq 10 to 500 Hz VFD2NFRQ 60 102
N.RPM VFD2 Nominal Motor rpm 50 to 30000 rpm VFD2Nrpm 1750 102
N.PWR VFD2 Nominal Motor HPwr 0 to 500 H.P. VFD2NPWR 20
a
103
M.DIR VFD2 Motor Direction 0=FWD, 1=REV VFD2MDIR 0 103
ACCL VFD2 Acceleration Time 0 to 1800 sec VFD2ACCL 30 103
DECL VFD2 Deceleration Time 0 to 1800 sec VFD2DECL 30 103
SW.FQ VFD2 Switching Frequency 0=1kHz, 1=4kHz, 2=8kHz, 3=12kHz VFD2SWFQ 2 103
TYPE VFD2 Type 0=LEN, 1=ANALOG VFD2TYPE 0 103