ZS zone sensors
ZS Sensors Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation Guide All rights reserved
9
ZS Standard ZS Plus ZS Pro ZS Pro with
motion sensor
ZS Pro-F
Specifications for ZS zone sensors
Sensing element
accuracy
Temperature Temperature only:
32° to 122°F (0° to 50°C):
±0.36°F (0.2°C)
Temperature if humidity is included:
50° to 104°F (10° to 40°C):
±0.54°F (0.3°C)
Humidity 10% to 90%: ±1.8% typical. Less than 0.5% drift per year.
CO
2
400 to 1250 PPM: ±30 PPM or 3% of reading, whichever is greater
1250 to 2000 PPM: ±5% of reading plus 30 PPM
See CO
2
sensor installation (page 11).
VOC 0 to 2,000 CO2 PPM Equivalent: ±100PPM
CO
2
sensor type
Non-Dispersive Infrared (NDIR)
Motion sensor type Passive infrared (PIR )