2 EASY
Installer setup page
overview.
Descriptions:
0-#: Call Monitor again
2-#: Exit out Debug State
0 : Power-on-to-unlock mode
1 : Power-off-to-unlock mode
Descriptions:
0-# Redial
1-# Tools
2-# Exits
* Cancel # Save
(0~3)
[ - ]
1. ID Code [0]
* Cancel # Save
(01~99)
[ - - ]
2. Unlock Timing [01]
* Cancel # Save
(0~1)
[ - ]
3. Unlock Output [0]
* Cancel # Save
(0~3)
[ - - - ]
4. Monitor Timing [600]
DMR18S Technical Menu-4-
The Debug State is the starting point for using all the applications on
DMR18S.
When door station is in
standby, press '#' key
Enter '9008', then enter the
Admin Code.(66666666
by default)
Debug state menu is
launched
1-#: Go to Tools setting
In
Debug State
, calling and conversation are available, you can
enter 0~9 to select the volume you require, see the following
image.
While working in debug
state, press "1#" to enter
tools page.
0 : Enter the room number to call the monitor
1 : Enter the room number + ‘#’ to call the monitor
* Note: In the diagram -
2) Shows setup of 2 digit calling.
CONFIGURATION
Debug State
Press NO.“1” to enter
'Installer Setup'.
1.ID Code:
Select 1 to enter
ID Code
setting page. You can input
0~3
to set as door 1 ~ door 4.
2.Unlock Timing:
Select 2 to enter
Unlock Timing
setting page,
setting range is from 01~99s.
3.Unlock Output:
Select 3 to enter
Unlock Output
setting page.
4.Monitor Timing:
Select 4 to enter
Monitor Timing
setting
page, the setting range is from 006~600s.
5.Doorplate Mode:
Select 5 to enter
Doorplate Mode
setting
page.
1) “0” mode is used as an example.