Settings
47
Settings
GB
CF model smoke evacuation fault
This test will lock the boiler in case there is a fault with the evacuation
of exhaust gases. Locking of the appliance is temporary and is
indicated by error code 6 01. After 12 minutes the boiler will start
its ignition procedure; if the conditions return to normal, the boiler
restarts normally, otherwise it locks and the cycle is repeated.
Important
In the event of incorrect operation or repeated problems,
switch o the electricity by setting the external switch to the
"OFF" position, close the gas tap and contact the After-Sales
department or a professional boiler technician to check the
cause of the malfunction and to x the exhaust gas outlet fault.
When maintenance work is carried out on the appliance, only use
genuine spare parts and follow the corresponding instructions
carefully. This appliance should never be disconnected, as this
could endanger the user.
Cleaning function
The PCB makes it possible to force the appliance to min or max
power. Activate the cleaning function by pressing Reset button
13 for 5 seconds; the boiler will switch to max heating power, and
the following appears on the display :
To select the function at maximum domestic hot water power,
turn the encoder; the following appears on the display :
To select the function at minimum power, turn the encoder; the
following appears on the display :
The function is automatically deactivated after 10 minutes or by
pressing the Reset button.
Note: the appliance can be forced to minimum or maximum
power from menu 7 (see the section on the display - setting -
diagnostics menu).
WARNING!
By activating the cleaning function, the temperature of
the water sent to the installation is limited to 88°C; caution
is therefore required with regard to low-temperature
installations.
Maximum Chauffage
Maximum Sanitaire
Puissance Minimum
Maximum Heating
Maximum D.H.W
Minimum Power

Table of Contents

Other manuals for CHAFFOTEAUX NIAGARA C 25 CF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CHAFFOTEAUX NIAGARA C 25 CF and is the answer not in the manual?

CHAFFOTEAUX NIAGARA C 25 CF Specifications

General IconGeneral
BrandCHAFFOTEAUX
ModelNIAGARA C 25 CF
CategoryBoiler
LanguageEnglish

Related product manuals