53
Settings
GB
menu
sub-menu
parameter
description value
default setting
0 SET TIME DATE LANGUAGE see user’s manual
1 SET TIMER see user’s manual
2
BOILER PARAMETER SETTING
2 1
Entering access code 222 turn the encoder clockwise to select 234
and press the MENU/OK button
2 2
BOILER GENERAL SETTING
2 2 0
Slow ignition 0 to 99 60 RESERVED FOR SAT
2 2 1
Minimum ambient temperature for
antifreeze activation
from 2 to 10 °C 5 Activated only with the modulating
peripheral device (optional)
2 2 2
NOT PRESENT
2 2 3
Underoor thermostat or zone 2 ambient
thermostat selection
0 = Floor safety thermostat
1 = Zone 2 ambient thermostat
0
2 2 4
NOT PRESENT
2 2 5
Heating ignition delay 0 = Deactivated
1 = 10 seconds
2 = 90 seconds
3 = 210 seconds
0 Activated only with zone 2 interface
(optional)
2 2 6
NOT PRESENT
2 2 7
NOT PRESENT
2 2 8
Boiler Version
ATTENTION ! Modify from 1 to 2 only with
connection to an external storage with
thermostat ON/OFF
0 to 5
0 = combi
1 = storage with NTC
2 = storage with thermostat
3 - 4 - 5 = NOT USED
1 RESERVED FOR TECHNICAL ASSISTANCE
Only if the PCB is changed
2 3 PARAMETRI RISCALDAMENTO PARTE 1
2 3 0
Absolute heating power adjustment
0 to 99 RESERVED FOR TECHNICAL ASSISTANCE
Only if the gas or PCB is changed. see
the "gas setting" table, information on
Starting
2 3 1
Maximum heating power setting 0 to 99 see the "gas setting" table, information
on Starting
2 3 2
NOT PRESENT
2 3 3
NOT PRESENT
2 3 4
NOT PRESENT
2 3 5
Selection of ignition delay type when
heating
0 = Manual
1 = automatic
1 see section on "gas setting"
2 3 6
Ignition delay when heating timer setting from 0 to 7 minutes 3
2 3 7
Post-circulation when heating from 0 to 15 minutes or OC (AC) 3
2 3 8
Circulation pump operating type
0 = Low Speed
1 = High Speed
2 = Modulating
2
2 3 9
Setting
the Delta T
Circulation pump
modulation
from 10 to 30 °C 20 to be set with operation of the
circulation pump in modulating mode
These parameters allow the ow and backow temperature dierence to be set, which determines whether the
circulation pump switches from low to high speed
E.g.: param. 239 = 20 and ∆T > 20°C- the circulation pump runs at high speed. If ∆T < 20 - 2°C the circulation pump runs
at low speed. The minimum waiting time for changing speed is 5 minutes.