2
Normal use, installation and transportation, storage conditions
2.1 Conditions of use, transportation and storage
   1. Use the ambient temperature (-10~+45)°C, derate use between 45°C~55°C, derate use by 1% for every
  1°C increase in temperature;
   2. Relative humidity (5~95)% RH;
   3. Storage temperature -25°C~ + 55°C ,
   4. If the altitude is above 1000 meters, please derate at the rate of 1 % for every 100m increase , but not 
  more than 3000m;
   5. Indoors , without direct sunlight, without dust, corrosive gas, flammable gas, oil mist, water vapor, 
  dripping water or salt,
2
   6. (2~9)Hz amplitude ≤ 0.3mm, (9- 200)Hz vibration acceleration ≤5.8m/ s  ;
note: Inverters stored for a long time must undergo a power-on test within 2 years. When powering on, use a voltage 
           regulator to slowly increase to the rated value, and power on for 1 hour without load, otherwise there is a risk 
           of electric shock and explosion.
2.2 Installation conditions
   When using the inverter, please pay attention to the installation spacing and distance requirements, as 
shown in Figure 2.1 :
Figure 2.1 Schematic diagram of inverter installation
003
NVF2G-S Series Inverter User's Guide