E.OT
Motor over 
temperature fault
1. The wiring of the motor temperature 
sensor is loose
Check motor temperature sensor 
wiring
2. Motor temperature is too high
Increase the carrier frequency or take 
other measures to dissipate heat from 
the motor
error code
Fault type
Possible cause of failure
Countermeasures
E. UV
Undervoltage fault
Grid voltage is low
Check input power
E.OL3
Buffer supply 
overload
The bus voltage fluctuates up and down at 
the undervoltage point
seek service
E. StG
Motor to ground 
short circuit fault
Motor short circuit to ground
Check the motor and cables
E.CbC
Wave-by-wave 
current limiting 
fault
1. The load is too large or the motor stalls
Reduce load and check motor condition
2. The selection of the frequency converter 
    is too small
Choose a frequency converter with a 
higher power rating
E.INV
Inverter hardware 
overcurrent fault
Refer to overcurrent fault Refer to overcurrent fault
E.LL
load drop fault
The operating current of the inverter is 
less than the set value of FE.18
Check if the load is off
Set the detection parameters 
reasonably according to the situation
A short circuit of the braking resistor of the inverter may cause damage to the braking unit of the 
inverter.
Notice
10.7 Operation exception handling
Table 10.4 Operation exception handling methods
 
Enter the user password correctly
Phenomenon condition Possible Causes
Countermeasures
The operator 
panel is not 
responding
Individual keys or 
all keys do not 
respond, or the 
panel prompts 
"ErCOC"
The operation panel lock 
function takes effect
In the state of stopping or running parameters, first 
press and hold the PRG key, and then continue to 
press ▼ to unlock 
Power off the inverter completely and then power 
on again
Check the cable and replug it
Poor connection of operation 
panel connection wire
Replace the operation panel or call for service
The function code cannot be 
modified
Cannot be 
modified in 
running state
This function code cannot 
be modified in the running 
state
Modify while down
Some function 
codes cannot be 
modified
Function code F7.03 is set to 
1 or 2
Change F7.03 to 0
This function code is the 
actual detection value
Actual parameters cannot be modified by users
Press MF no 
response
The operation panel lock 
function is in effect or other
See "Operation Panel Not Responding" Solution
Cannot enter 
after pressing 
PRG, the function 
code display 
status shows 
0000
With user password
seek service
The function 
code cannot
be modified