Feedback quantity
Given value
Output
frequency
Time
Time
Deviation limits
Differential gain
Kd is larger
Differential gain
Kd is less
Proportional gain
Kp is larger
Proportional gain
Kp is less
Integral gain
Ki is larger
Integral gain
Ki is less
Figure 8-2-8 Influence of Process PID Parameters
8.2.7 Communication setting main frequency
   See Chapter 9 RS485- Modbus communication instructions for details .
8.2.8 Input setting of auxiliary frequency command
   Set parameter F0.03 to select the auxiliary frequency command input, which is the same as the main 
frequency command input selection method, the specific parameter selection and setting process can refer to 
"8.2.1 Select the input method of the main frequency command".
8.2.9 Select main and auxiliary frequency superposition command
   The relationship between the target frequency and the main and auxiliary frequency commands can be set 
by parameter F 0 . 04 .
function code
name
default value
Predetermined area
Parameter Description
F0.03
Auxiliary frequency 
source selection
0
0
Digital setting (F 0.05 )
1 A I1
2 A I2
3
reserve
4
reserve
5
multi-segment command
6
Simple PLC
7
Closed-loop PLC
8
Communication given frequency
F0.04
Main and 
auxiliary 
frequency 
source 
operation
0x0000
0x0000 ~0x0031
function 
code
name
default 
value
Predetermined 
area
Parameter Description
Units: frequency source selection
0: main frequency selection
1: operation result
    Tens place: main and auxiliary frequency source 
operation
0: main + auxiliary
1: main + auxiliary
2: The maximum value of the two is MAX
3: The minimum value of both MIN
045
NVF2G-S Series Inverter User's Guide