NVF5 Series User Manual        Appendix A RS485-MODBUS 
Communication Instructions 
Group number mapping of the inverter function parameter is the upper bytes of 
Modbus register address (0~F corresponding values are 0x00~0x0F); Group Index 
(parameter number in the group) mapping is the lower bytes of Modbus register address 
(00~99 corresponding values are 0x00~0x63). When data is only required to be stored in 
RAM (i.e.,data not stored on power-down), the highest position of the address is “1”.   
For example
The corresponding register address of Parameter“F5.27”is“0x051B”
:
 
1
)
Corresponding address is “0x851B”when data only be stored to RAM. 
2
)
Corresponding address is “0x051B”when data only be stored to 
EEPROM(Data stored on power-down). 
A.5.3 Obtain the parameter attribute of the inverter function code   
Parameter attribute of the inverter function code can be obtained by 0x04 command 
code. Attribute definition format is shown in Table A.2.。 
Table A.2 Data format definition when reading parameter attribute 
Maximum value (upper byte) 
Maximum value (lower byte) 
Minimum value (upper byte) 
Minimum value (lower byte) 
Current value (upper byte) 
Current value (lower byte) 
Parameter attribute value (upper byte); refer to Table A.3 
Parameter attribute value (lower byte); refer to Table A.3 
Table A.3 Definitions of parameter attribute value (bit) 
Bit Definition  Bit Value  Decimal Value  Explanation 
15~14bit: Display 
Type 
00  0  Decimal 
13~11bit: Modify 
Attribute 
000  0 
Writable and readable at any 
time 
Modifiable in the stop state 
011  3 
Writable and readable with an 
enterprise password 
100  4 
Readable with an enterprise 
password 
101  5 
Writable and readable with an 
user 
10~8bit: Data 
000  0  8-bit unsigned bit data type 
- 104 -