NVF5 Series User Manual     Chapter 6 Parameter Function Description 
Set parameter  F1.00=0,directly start inverter,suitable for most kinds of load.Set 
parameter F1.01-direct starting frequency:suitable for some constant torque load. 
Freq. Hz
Setting
Freq.
Start Freq.
time
Start Freq. Holding time
 
Figure 6-3-1 Directly Start Time Sequence Chart 
  First Braking then Starting from Starting Frequency 
Set parameter F1.00=1,Set parameter F1.01  ~  F1.04DC brake function before 
start,suitable for motor rotate when start . 
Freq. 
Hz
Time
t
Output vol.
(RMS value)
Time
t
DC 
injection 
brake 
level
RUN 
command
DC injection 
brake time
 
Figure 6-3-2 First Braking then Starting Time Sequence Chart 
  Speed Tracking(including direction discrimination) and Restart 
Set parameter F1.00=2,the start mode of the inverter is speed tracking and restart
(The inverter first judge the speed and direction of the motor, and then starts with the 
tracking motor frequency)suitable for large inertia load. If the motor is still running by large 
inertia load when the inverter start, the over-current can be avoided by adopting speed 
tracking and restarting. 
- 58 -