8 - INSTALLER SETTINGS
N° Description Possible choices
24
Cut-off on setpoint:
Makes a stop or not the ventilation setpoint
Unit -
Allows two modes of operation:
-YES: switching off the fan to obtain the desired
- NO: your installation will be in permanent ventilation (limits the
stratication phenomenon in WINTER, ensures air circulation
ETA) .
Min -
Max -
Defaut Oui
Increment -
25
Temporisation de la post-
ventilation:
Sets the delay time
Unit mn
Sets the duration of post - ventilation to the judgment of the
electric battery.
This delay serves to remove all the calories emitted by inertia
after stopping the electric battery.
Min 1
Max 20
Defaut 2
Increment 1
28
Number of electric power stage
controlled:
Unit -
Sets the number of power stage electric battery to drive:
H4350: 9.6 kW 2 oors
H4400: 18.9 kW 2 oors
H4500: 28.8 kW 2 oors
H4500: 43.2 kW 3 oors
Min 2
Max 3
Defaut 2
Increment -
29
Number of controlled power box:
Sets the number of slaves controlled by a
master controller:
Unit -
This parameter denes the number of slave box controlled by a
controller BOX ELEC Eco +
The home setting must match the position of the switches (see
page 5)
Min 1
Max 3
Defaut 1
Increment -
EN-25 BOX ELEC Eco+