8 - INSTALLER SETTINGS
To change from "USER" mode (restricted access) to "INSTALLER" mode (all settings), press both arrows
on menu scroll button for 5 seconds.
Reverts to "USER" mode if no buttons are pressed for a period of 30 seconds.
N° Description Possible choices
10
Temperature:
Used to display the temperature measured
by the sensor
Unit °C
Read-onlyMin 0
Max 51
Defaut -
Increment -
11
Level:
To display whether the fan
motor assembly is on or off
Unit -
Read-only
Min OFF
Max ON
Defaut
Increment -
12
Time:
Used to set the time
Unit hh.mm
Required for proper operation of the installation
01 when the setting is on tIME.
Min 00.00
Max 23.59
Defaut 18
Increment 0.2
13
WINTER gradient:
Setting the slope to reach the set point in
operation WINTER
Unit °C
The steeper the slope is large (close to 15 °C), more engagement of the
power stages electric battery is progressive. Disadvantage, the set T ° is
to be a long reach .
The steeper the slope is short (close to 1 °C), more engagement of the
power stages electric battery is reactive . Drawback system close to a
regulation in All- or - Nothing .
In SUMMER operating mode, only the fan is on.
Min 1
Max 15
Defaut 5
Increment 0.2
14
SUMMER slope:
Setting the slope to reach the operating
setpoint SUMMER
Unit °C
Min 1
Max 15
Defaut 8
Increment 1
15
Deviation ECO:
offset adjustment from the set point by
utilation comfort
Unit °C
Operating WINTER downward shift:
eg Comfort setpoint 20 °C, offset set to 3 °C setpoint ECO = 17
°C
Operating ETE upward shift:
Example: Comfort setpoint 24 °C, offset set to 3 °C setpoint ECO =
27 °C
Min 1
Max 5
Defaut 3
Increment 0.5
16
Temperature setpoint
in use frost
Unit °C
From 5 to15°C
In SUMMER operating mode, the Frost Protection mode is off, it is then
converted to ECO operation mode
Min 5
Max 15
Defaut 8
Increment 0.5
17
Temperature Sensor Calibration:
Corrects the measurement probe
Unit °C
-
Min -5
Max 5
Defaut 0
Increment 0.2
BOX ELEC Eco+ EN-24