4.9.15 - SCHEDULE menu
NAME DESCRIPTION
OCC1P01S Unit on/off time schedule
OCC1P02S Unit setpoint selection time schedule
4.9.16 - HOLIDAY menu
NAME DESCRIPTION
HOLDY_01 Holiday period 1
HOLDY_02 Holiday period 2
HOLDY_03 Holiday period 3
HOLDY_04 Holiday period 4
HOLDY_05 Holiday period 5
HOLDY_06 Holiday period 6
HOLDY_07 Holiday period 7
HOLDY_08 Holiday period 8
HOLDY_09 Holiday period 9
HOLDY_10 Holiday period 10
HOLDY_11 Holiday period 11
HOLDY_12 Holiday period 12
HOLDY_13 Holiday period 13
HOLDY_14 Holiday period 14
HOLDY_15 Holiday period 15
HOLDY_16 Holiday period 16
4.9.17 - BRODCAST menu
NAME FORMAT DEFAULT UNIT DESCRIPTION
ccnbroad 0/1/2 2 - Activates the broadcast
0 = deactivated, 1= broadast during holidays at the network,
2 = broadcast during holidays, machine only
oatbusnm 0 to 239 0 - Broadcast of the outside temperature
Bus number of the machine with the outside temperature
oatlocad 0 to 239 0 - Element number of the machine with the outside temperature
dayl_sel Disable/Enable Disable - Activation summer time, winter time
Summer time
startmon 1 to 12 3 - Month
startdow 1 to 7 7 - Day of the week (1 = Monday)
startwom 1 to 5 5 - Week of the month
Winter time
stopmon 1 to 12 10 - Month
stoptdow 1 to 7 7 - Day of the week (1 = Monday)
stopwom 1 to 5 5 - Week of the month
4.9.18 - GENCONF menu
NAME FORMAT DEFAULT UNIT DESCRIPTION
lead_cir 0/1/2 0 - Circuit loading sequence
0 = auto, 1 = A first, 2 = B first
seq_typ No/Yes No - Loading sequence by circuit
ramp_sel No/Yes No - Ramp loading sequence
off_on_d 1 to 15 1 min Start-up delay
nh_limit 0 to 100 100 % Capacity limitation in night mode
nh_start 00:00 to 24:00 00:00 - Night mode start hour
nh_end 00:00 to 24:00 00:00 - Night mode stop hour
bas_menu 0 to 3 0 - Basic menu configuration
0 = total access
1 = access to the alarm menu by password
2 = access to the setpoint menu by password
3 = combination of 1 and 2
synoptic No/Yes No - Synoptic diagram displayed
4.9.19 - PUMPCONF menu
NAME FORMAT DEFAULT UNIT DESCRIPTION
pump_seq 0/1/2/3/4 0 - Heat exchanger pump sequence
0 = no pump
1 = one pump
2 = two pumps auto
3 = pump 1 manual
4 = pump 2 manual
pump_del 24 to 3000 48 hours Rotation time between pumps
pump_per No/Yes No - Pump seizure protection
pump_sby No/Yes No - Pump shutdown when the unit is in standby
pump_loc No/Yes Yes - Flow rate verification when the pump has shut down
4 - SETTING UP PRO-DIALOG+ CONTROL
EN - 13 EREBA ACCESS