EasyManua.ls Logo

CIAT PRO-DIALOG+ - HCCONFIG Menu Settings; USERCONF Menu Options

CIAT PRO-DIALOG+
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.9.20 - HCCONFIG menu
NOM FORMAT DEFAULT UNIT DESCRIPTION
auto_sel No/Yes No - Automatic change-over selection
cr_sel 0 to 2 0 - Cooling reset selection
hr_sel 0 to 2 0 - Heating reset selection
1 = outside temp., 0 = none, 2 = delta T
heat_th -20 to 0 -15 °C Outside temperature threshold cooling mode
boil_th -15 to 15 -10 °C Outside temperature threshold for the boiler
ehs_th -5 to 21.2 5 °C Outside temperature threshold for electric heater stages
both_sel No/Yes No - Heating or cooling command selection for HSM
ehs_back No/Yes No - 1 backup electric heater stage
ehs_pull 0 to 60 0 minutes Delay before start-up of the first electric heater stage
ehs_defr No/Yes No - Quick electric heat stages for defrost
4.9.21 - RESETCFG menu
NAME FORMAT DEFAULT UNIT DESCRIPTION
COOLING RESET
oatcr_no -10 to 51.7 -10 °C Outside temperature for no reset
oatcr_fu -10 to 51.7 -10 °C Outside temperature for maximum reset
dt_cr_no 0 to 13.9 0 ^C Delta T for no reset
dt_cr_fu 0 to 13.9 0 ^C Delta T for maximum reset
cr_deg -16.7 to 16.7 0 ^C Cooling reset value
HEATING RESET
oathr_no -10 to 51.7 -10 °C Outside temperature for no reset
oathr_fu -10 to 51.7 -10 °C Outside temperature for maximum reset
dt_hr_no 0 to 13.9 0 ^C Delta T for no reset
dt_hr_fu 0 to 13.9 0 ^C Delta T for maximum reset
hr_deg -16.7 to 16.7 0 ^C Heating reset value
4.9.22 - USERCONF menu
NAME FORMAT DEFAULT UNIT DESCRIPTION
language 0 to 4 0 - Language selection
English = 0, Spanish = 1, French = 2, Portuguese = 3, Italian = 4,
Translation = 5
use_pass 1 to 9999 11 - User password
4.9.23 - DATETIME menu
NAME FORMAT DEFAULT UNIT DESCRIPTION
hour 0 to 24 hours Hour
minutes 0 to 59 minutes Minutes
dow 1 to 7 Day of the week
tom_hol No/Yes No - Holiday tomorrow?
tod_hol No/Yes No - Holiday today
dlig_off No/Yes - Winter time change-over active?
dlig_on No/Yes - Summer time change-over active?
d_of_m 1 to 31 Day of the month
month 1 to 12 Month
year 0 to 99 Year
4.9.24 - Menu CTRL_ID
NAME FORMAT DEFAULT UNIT DESCRIPTION
elemt_nb 1 to 239 1 - Element number
bus_nb 0 to 239 0 - Bus number
baudrate 9600 to 38400 9600 - Communication speed
PRO-DIALOG+ Description
CSA-SR-20H430NN
-
Software version
Serial number
4 - SETTING UP PRO-DIALOG+ CONTROL
EREBA ACCESS EN - 14