Statement 1005—Circuit Breaker
This product relies on the building's installation for short-circuit (overcurrent)
protection. Ensure that the protective devices is rated not greater than (see the
table below).
Warning
Table 1:
Circuit Breaker CurrentPower Supply CurrentN3000 Chassis PIDDC Power Supply PID
20A15-8AN3K-C3016XX-XXXX
N3K-C3048XX-XXXX
N3K-C3064XX-XXXX
N3K-C3132XX-XXXX
N3K-C172XX-XXXX
N2200-PDC-400W
NXA-PDC-500W
NXA-PDC-500W-B
5A3AN3K-C3016XX-XXXX
N3K-C3048XX-XXXX
N3K-C3064XX-XXXX
N3K-C3132XX-XXXX
N3K-C172XX-XXXX
NXA-PHV-500W
30A23-16A or 23-18AN3K-C132C-Z
N3K-C3232CXX-XXXX
N3K-C3164XX-XXXX
N3K-C31108PCXX-XXXX
N3K-C31128XX-XXXX
N3K
UCSC-PSU-930WDC
NXA-PDC-930WDC-PI
NXA-PDC-930WDC-PE
UCSC-PSU-6332-DC
10A6A or 7AN3K-C3132C-Z
N3K-C3164XX-XXXX
N3K-C3264QX-XXXX
N3K-C34180YC-XXXX
N9K-PUV-1200W
• There is adequate clearance around the rack to install the switch and to allow for unimpeded airflow.
• You have the following equipment in addition to the switch and the kits shipped with the switch:
• Eight customer-supplied 12-24 or 10-32 screws (required for attaching slider rails and mounting
bracket to the mounting rails)
• Number 1 and number 2 Phillips screwdrivers with torque capability
Cisco Nexus 3000 Series Hardware Installation Guide
30
Installing the Chassis
Preparing to Install the Chassis