Step 14S: Set Relay 2 operation using V or W.The choices are the same as Step 11S, with the addition of
ERROR MONITOR. If set to ERROR MONITOR, the relay closes whenever the valve enters error mode, and
immediately deactivates when error mode is exited.
If set to OFF, Steps 15S and 16S will not be shown.
Press NEXT to go to Step 15S. Press REGEN to return to previous step.
STEP 14S
STEP 15S
Step 15S: Set Relay 2 SETPOINT Time or Volume using the V or W buttons. The choices are the same as Step
12S.
Press NEXT to go to Step 16S. Press REGEN to return to previous step.
STEP 16S
Step 16S: Set Relay DURATION TIME using the V or W buttons.
• If TIME is selected in Step 14S the relay will deactivate after the time set has expired.
• If VOLUME or REGEN VOLUME is selected in Step 14S the relay will deactivate after the time set has expired
or after the meter stops registering ow, whichever comes rst.
Press NEXT to go to Step 17. Press REGEN to return to previous step.
Step 17S: Set scheduled service alarm using the V or W. Available options are OFF, TIME, ON GAL or BOTH.
Selecting OFF disables this feature. If OFF is selected press NEXT to exit OEM Softener System Setup. If TIME,
ON GAL or BOTH is selected press NEXT to select the TIME and/or ON GAL values. See Steps 17S and/or 18S.
Press REGEN to return to the previous step.
Step 18S: Time remaining until Service Alarm generation. Only appears if TIME or BOTH is set in Step 16S. To
change duration time, use V or W to select the new value. Press NEXT to exit OEM Softener System Setup or go
to Step 19S if BOTH was selected in Step 17S. Press REGEN to return to the previous step.
Step 19S: Volume remaining until Service Alarm generation. Only appears if GAL or BOTH is set in Step 17S.
To change the volume between service calls, use V or W to select the new value. Press NEXT to go to Step 20S.
Press REGEN to return to the previous step.
STEP 17S
STEP 18S
STEP 19S
RETURN TO NORMAL MODE
Step 20S: Status display only, if Step 17S is set to TIME or BOTH. Shows time remaining to Service Alarm. Can
be reset to the initial value by pressing V and W for approximately 3 seconds. Press NEXT to exit OEM Softener
System Setup or to go to Step 21S. Press REGEN to return to previous step.
STEP 20S
Step 21S: Status display only, if Step 17S is set to TIME or BOTH. Shows time remaining to Service Alarm. Can
be reset to the initial value by pressing V and W for approximately 3 seconds. Press NEXT to exit OEM Softener
System Setup. Press REGEN to return to previous step.
STEP 21S