CLEAN BURN MODELS: CB-1750, CB-2500, and CB-3250
MULTI-OIL FURNACES
with CB-525-S2 BURNER
PUBLICATION DATE: 05/12/14, Rev. 14 CLEAN BURN PART # 43195
IMPORTANT FOR U.S. INSTALLATIONS: All installations must be made in accordance with state and local codes
which may differ from the information provided in this manual. Save these instructions for reference.
IMPORTANT FOR CANADIAN INSTALLATIONS: These instructions have been reviewed and accepted by
Underwriters' Laboratories of Canada as being appropriate for the installation of the ULC labelled products
identied herein. The use of these instructions for the installation of products NOT bearing the ULC label and
NOT identied herein may result in an unacceptable or hazardous installation.
IMPORTANT FOR CANADIAN INSTALLATIONS: The installation of this equipment is to be accomplished by
qualied personnel and in accordance with the regulation of authorities having jurisdiction and CSA Standard B 139,
Installation Code for Oil Burning Equipment.
WARNING: DO NOT assemble, install, operate, or maintain this equipment without rst
reading and understanding the information provided in this manual. Installation and
service must be accomplished by qualied personnel. Failure to follow all safety precautions
and procedures as stated in this manual may result in property damage, serious personal injury
or death.
OPERATOR'S MANUAL
IN THE VICINITY OF THIS OR ANY APPLIANCE !!
OR OTHER FLAMMABLE VAPORS AND LIQUIDS
DO NOT STORE GASOLINE
FOR YOUR SAFETY -
ENERGY SYSTEMS
www.cleanburn.com
I88435-D
USED-OIL BURNING
APPLIANCE
USED OIL-FIRED
FURNACE
LISTED
#MH15393 (N)

Table of Contents

Questions and Answers

  • R
    Rachel BaileyAug 15, 2025
    Why CLEAN BURN Furnace pump will not prime but the motor is running?
    • B
      Brandon HodgesAug 15, 2025
      If the CLEAN BURN Furnace pump will not prime but the pump motor is running, the possible causes are: * Leaks in the suction line. * Improper pump installation. * Dry pump gears. * Damaged pump seal. * Closed ball valve. * Dirty canister filter. * Dirty check valve. * Damaged or worn-out pump. Solutions include ensuring the suction line is airtight, filling the pump head with oil before starting, filling the oil line and priming the pump, replacing the pump or seal if damaged, opening the ball valve, and cleaning the canister filter and check valve. If these steps don't work, the pump may need replacement.
  • M
    Mary LarsenAug 18, 2025
    What to do if CLEAN BURN CB-1750 pump won't prime and the motor is not running?
    • J
      Joanna ChapmanAug 18, 2025
      If the CLEAN BURN Furnace pump will not prime and the pump motor is NOT running, it could be due to: 1. No power on the pump circuit from the burner. 2. The pump motor has shut off on thermal overload. To resolve this, start the burner and adjust the air pressure regulator to 15 PSI to check if the pump circuit activates. If not, troubleshoot the pump circuit from the burner to the pump, checking for power at the brown wire on the air pressure switch. If the pump motor has overheated, wait for it to cool down and reset. Also, check the coupling adjustment to ensure free shaft movement.
  • J
    Jimmy RiggsAug 22, 2025
    How to fix CLEAN BURN CB-1750 when burner won’t run and power light is off?
    • P
      Paula ParkAug 22, 2025
      If the CLEAN BURN Furnace burner won’t run at all and the green power light is NOT ON, check the following: 1. Circuit breaker/main switch open. 2. Blown fuse/breaker. 3. Damaged or improperly plugged-in burner cable. To solve this, close the circuit breaker/switch, have an electrician check the electrical system, and inspect the burner cable.
  • M
    Michael GuerraAug 26, 2025
    What to do if CLEAN BURN Furnace burner ignites, but will not stay running?
    • R
      Rebecca WilsonAug 26, 2025
      If the CLEAN BURN Furnace burner ignites but shuts off on reset within 15 seconds, it could be due to several reasons: * A fuel delivery problem. * A dirty cad cell. * Loose cad cell wires. * Damaged cad cell/cad cell wires. * The primary control not receiving the proper ohm signal from the cad cell. Possible solutions include cleaning or replacing the cad cell and wires, ensuring proper wire connections at the "F" terminals on the oil primary control, and checking the cad cell position to ensure it looks straight through the central hole in the retention head. Also, verify the position of the retention head.
  • H
    hgarciaAug 28, 2025
    Why does my CLEAN BURN Furnace burner shut off on reset periodically?
    • B
      Brandy HutchinsonAug 28, 2025
      If the CLEAN BURN Furnace burner ignites and runs properly, but shuts off on reset periodically, suspect these causes: 1. Air in the suction oil line due to leaks at the fittings. 2. Air trapped in a high point in the pressure oil line. To resolve this, vacuum test the pump and properly seal the suction line fittings to eliminate air leaks. Also, bleed the air out of the pressure oil line.
  • G
    gandersonSep 1, 2025
    What to do if CLEAN BURN Furnace burner ignites and shuts off later?
    • S
      scoxSep 1, 2025
      If the CLEAN BURN Furnace burner ignites and then shuts off on reset sometime later, it could be due to: * Air in the fuel supply. * The primary control not receiving the proper ohm signal from the cad cell. * Insufficient air pressure. * A cold heater block. * Fouled electrodes. To address this, prime the pump, check for a proper ohm signal, adjust the air regulator for proper air pressure, ensure the heater block remains hot by not shutting off power to the furnace overnight (instead, turn the wall thermostat to OFF), and clean the electrodes and retention head if oil residues have built up.
  • M
    Michael DavenportSep 4, 2025
    What to do if CLEAN BURN Furnace burner won’t run but the power light is on?
    • E
      erika81Sep 4, 2025
      If the CLEAN BURN Furnace burner won’t run at all and the green power light is ON, the possible causes are: 1. Oil primary control has shut down on safety reset. 2. Wall thermostat is not operating. 3. Heater block is not heating up. 4. F-120 proving switch has not closed. 5. Oil primary control terminals are not wired correctly. 6. Oil primary control is damaged. 7. The L-200 or L-290 limit switches have opened. To troubleshoot, reset the oil primary control, check the wall thermostat and cable, ensure the heater block is hot, check the F-120 proving switch for power, verify the oil primary control wiring, and replace the oil primary control if necessary. Also, test the limit switch for power.
  • J
    Jeremy CooperSep 7, 2025
    Why does my CLEAN BURN Furnace blower motor run all the time?
    • C
      Chelsea HuffmanSep 8, 2025
      If the CLEAN BURN Furnace blower motor runs all the time, it could be due to: 1. Incorrectly wired blower motor circuit. 2. For CB-2500/3250 models only: a blower relay stuck in the closed position. To troubleshoot, refer to the wiring diagram and ladder schematic to check the blower circuit. Also, test the blower motor contactor and replace it if it does not open when the power is turned OFF.
  • T
    Timothy WallaceSep 12, 2025
    What to do if CLEAN BURN CB-1750 blower motor will not run?
    • T
      tmccarthySep 12, 2025
      If the CLEAN BURN Furnace blower motor will not run, possible causes include: 1. Incorrect wiring of the blower motor. 2. A defective fan/blower switch. 3. The blower motor overheating and shutting down on thermal reset. 4. For CB-2500/3250 models only: the blower relay not closing. To troubleshoot, check the fan motor wiring, replace the fan/blower switch if defective, allow the blower motor to cool down if it has overheated, and test the blower motor contactor, checking for proper voltage at the L1/L2 lugs and the orange wire on the coil.

Summary

SECTION 1: INTRODUCTION

For Your Safety

Details critical safety warnings, precautions, and hazard symbols used.

SECTION 3: FURNACE ASSEMBLY

Installing the Blower Assembly

Step-by-step guide for installing the blower assembly for CB-1750/2500 models.

Installing the CB-3250 Blower Assembly

Detailed instructions for mounting and wiring the CB-3250 blower.

Installing the Burner

Procedures for checking burner nozzle/electrodes and mounting the burner.

Installing the Connector Block, Oil Line Tubing, and Air Line Tubing

Instructions for connecting the oil and air lines to the burner assembly.

SECTION 4: FURNACE INSTALLATION

Selecting a Location

Guidelines for choosing a safe and appropriate location for furnace installation.

Mounting the Furnace

Instructions for mounting the furnace via ceiling, raised platform, or floor.

Oil Tank Installation Specifications

Detailed requirements for safe and compliant installation of used oil storage tanks.

Installing the Metering Pump

Procedures for mounting and positioning the metering pump for optimal function.

Wiring the Furnace and Pump

Guidance on electrical connections for the furnace and metering pump.

Installing the Suction Oil Line Components

Steps for correctly installing the oil line from the tank to the pump.

SECTION 5: METERING PUMP PRIMING

SECTION 6: STARTING AND ADJUSTING THE BURNER

SECTION 7: RESETTING THE FURNACE AND BURNER

SECTION 8: ADJUSTING THE DRAFT OVERFIRE

SECTION 9: MAINTENANCE

SECTION 10: TROUBLESHOOTING

Troubleshooting Tables

Detailed tables listing problems, causes, and corrective actions.

APPENDIX B

CB-1750 Furnace Wiring Diagram

Detailed wiring diagram for the CB-1750 furnace model.

CB-2500 Furnace Wiring Diagram

Detailed wiring diagram for the CB-2500 furnace model.

CB-3250 Furnace Wiring Diagram (115 Volts)

Wiring diagram for the CB-3250 furnace at 115 Volts.

Ladder Schematic for CB-1750

Ladder logic schematic for the CB-1750 furnace.

Ladder Schematic for CB-3250 (115 Volts)

Ladder logic schematic for CB-3250 at 115 Volts.

CLEAN BURN CB-1750 Specifications

General IconGeneral
BrandCLEAN BURN
ModelCB-1750
CategoryFurnace
LanguageEnglish