Tranquility
®
30
(TT) Series
Models TTD/H/V 026 - 072
60 Hz - HFC-410A
INSTALLATION, OPERATION,
& MAINTENANCE
97B0075N05
Revised: 18 July, 2013
Table of Contents
Model Nomenclature 3
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
Electrical - Line Voltage 20
Electrical - Power Wiring 22
Electrical - Power & Low Voltage Wiring 23
Electrical - Low Voltage Wiring 24
Electrical - Thermostat Wiring 26
Blower Performance Data 27
ECM Blower Control 28
Typical Wiring Diagram - Units with CXM Board
and ECM Fan Motor (Single Phase) 30
Typical Wiring Diagram - Units with
ClimaDry
®
(Single Phase) 31
Typical Wiring Diagram - Units with CXM Board, 32
ECM Fan Motor, and MPC (DDC) CONTROLS
(SINGLE PHASE) 32
CXM Controls 33
DXM Controls 34
Safety Features - CXM and DXM Controls 36
ClimaDry
®
Modulating Reheat Option 38
Unit Starting and Operating Conditions 41
Piping System Cleaning and Flushing 42
Unit and System Checkout 44
Unit Start-Up Procedure 45
ClimaDry
®
II Option Corrections
(When Operating in Non-ClimaDry
®
Mode) 46
Unit Operating Conditions 47
Preventive Maintenance 49
Functional Troubleshooting 50
Performance Troubleshooting 51
Start-Up Log Sheet 52
Functional Troubleshooting 53
Warranty (U.S. & Canada) 54
Warranty (International) 55
Revision History 56

Questions and Answers:

ClimateMaster Tranquility TTV049 Series Specifications

General IconGeneral
BrandClimateMaster
ModelTranquility TTV049 Series
CategoryHeat Pump
LanguageEnglish

Summary

Model Nomenclature

General Information and Safety

Safety

Essential safety warnings and precautions for installation and service.

Pre-Installation Procedures

Pre-Installation

Steps and checks required before beginning unit installation.

Horizontal Installation

Vertical Installation

Piping Installation

Installation of Supply and Return Piping

Comprehensive guidelines for connecting supply and return piping to the unit.

Water-Loop Heat Pump Applications

Commercial Water Loop Applications

Details on applying heat pumps in commercial water loop systems, including flushing and flow rates.

Ground-Loop Heat Pump Applications

Water Quality Standards

Ground-Water Heat Pump Applications

Electrical - Line Voltage

Electrical - Power Wiring

Electrical - Power & Low Voltage Wiring

Electrical - Low Voltage Wiring

Electrical - Thermostat Wiring

ECM Blower Control

Typical Wiring Diagram - CXM/ECM (Single Phase)

Typical Wiring Diagram - ClimaDry® (Single Phase)

Typical Wiring Diagram - CXM/MPC/DDC (Single Phase)

CXM Controls

DXM Controls

Safety Features - CXM and DXM Controls

Anti-short cycle protection

Protection against short cycling the compressor to prevent damage.

Fault Retry

How the control attempts to recover from faults, indicated by LED status.

Lockout

Control lockout mode, soft and hard reset procedures, and fault memory.

High pressure switch

Operation and effect of the high pressure switch on compressor operation.

Low pressure switch

How the low pressure switch is recognized as a fault after continuous open time.

Water coil low temperature (LT1)

LT1 fault condition and lockout based on water coil temperature limits.

Air coil low temperature (LT2)

LT2 fault condition and lockout based on air coil temperature limits.

Condensate overflow

Condensate overflow fault recognition and monitoring.

Over/under voltage shutdown

Safety shutdown due to voltage outside acceptable range, with self-resetting capability.

Safety Features - CXM and DXM Controls Continuation

Diagnostic Features

Using LEDs on CXM/DXM boards to diagnose control status and faults.

ClimaDry® Modulating Reheat Option

ClimaDry® Sequence Of Operation

How ClimaDry® operates in cooling, reheat, and heating modes with various thermostats.

UNIT STARTING AND OPERATING CONDITIONS

Unit Starting and Operating Conditions

Piping System Cleaning and Flushing

Piping System Cleaning and Flushing Procedures

Flushing/Purging Units with ClimaDry®

Procedure for flushing and purging ClimaDry® coils, including valve operation.

Unit and System Checkout

Unit Checkout

Checklist of pre-power checks for unit components, wiring, and fan.

System Checkout

Checklist for system-level checks, including water temperature, pH, and controls.

Unit Start-Up Procedure

Unit Operating Conditions

Unit Operating Conditions Data

Preventive Maintenance

Water Coil Maintenance

Procedures for maintaining water coils in direct ground water and other water loop applications.

Filters

Importance of clean filters for performance and recommended maintenance schedule.

Functional Troubleshooting

Main power problems

Checks for issues related to main power supply, circuit breakers, and transformer.

HP Fault Code 2

Troubleshooting steps for High Pressure fault code 2, including refrigerant charge and switches.

High Pressure

Possible causes and solutions for high pressure conditions in the system.

LP/LOC Fault Code 3

Troubleshooting steps for Low Pressure/Loss of Charge fault code 3.

Low Pressure / Loss of Charge

Addressing low pressure or loss of charge issues in the system.

LT1 Fault Code 4

Troubleshooting steps for LT1 Fault Code 4 related to water coil low temperature.

LT2 Fault Code 5

Troubleshooting steps for LT2 Fault Code 5 related to air coil low temperature.

Condensate Fault Code 6

Troubleshooting steps for Condensate Fault Code 6 related to drainage issues.

Over/Under Voltage Code 7

Troubleshooting steps for Over/Under Voltage fault code 7.

Unit Performance Sentinel Code 8

Troubleshooting steps for Unit Performance Sentinel fault code 8.

Swapped Thermistor Code 9

Troubleshooting steps for Swapped Thermistor fault code 9.

Only Fan Runs

Troubleshooting when only the fan operates and the compressor does not.

Only Compressor Runs

Troubleshooting when only the compressor runs and the fan does not.

Unit Doesn't Operate in Cooling

Steps to take when the unit fails to operate in cooling mode.

Functional Troubleshooting Issues

Performance Troubleshooting

Addressing issues related to insufficient capacity or poor performance in heating/cooling.

Insufficient capacity

Diagnosing and resolving insufficient cooling or heating capacity issues.

High Head Pressure

Identifying causes and solutions for high head pressure conditions.

Functional Troubleshooting Analysis