Tranquility
®
30
(TT) Series
Models TTD/H/V 026 - 072
60 Hz - HFC-410A
INSTALLATION, OPERATION,
& MAINTENANCE
97B0075N05
Revised: 18 July, 2013
Table of Contents
Model Nomenclature 3
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
Electrical - Line Voltage 20
Electrical - Power Wiring 22
Electrical - Power & Low Voltage Wiring 23
Electrical - Low Voltage Wiring 24
Electrical - Thermostat Wiring 26
Blower Performance Data 27
ECM Blower Control 28
Typical Wiring Diagram - Units with CXM Board
and ECM Fan Motor (Single Phase) 30
Typical Wiring Diagram - Units with
ClimaDry
®
(Single Phase) 31
Typical Wiring Diagram - Units with CXM Board, 32
ECM Fan Motor, and MPC (DDC) CONTROLS
(SINGLE PHASE) 32
CXM Controls 33
DXM Controls 34
Safety Features - CXM and DXM Controls 36
ClimaDry
®
Modulating Reheat Option 38
Unit Starting and Operating Conditions 41
Piping System Cleaning and Flushing 42
Unit and System Checkout 44
Unit Start-Up Procedure 45
ClimaDry
®
II Option Corrections
(When Operating in Non-ClimaDry
®
Mode) 46
Unit Operating Conditions 47
Preventive Maintenance 49
Functional Troubleshooting 50
Performance Troubleshooting 51
Start-Up Log Sheet 52
Functional Troubleshooting 53
Warranty (U.S. & Canada) 54
Warranty (International) 55
Revision History 56

Questions and Answers

  • M
    Maria ThompsonAug 18, 2025
    How to troubleshoot main power problems in ClimateMaster Heat Pump?
    • S
      Samuel PhillipsAug 18, 2025
      If your ClimateMaster Heat Pump has main power problems and the Green Status LED is off, check the line voltage circuit breaker and disconnect. Also, check for line voltage between L1 and L2 on the contactor, for 24VAC between R and C on CXM/DXM, and the primary/secondary voltage on the transformer.
  • M
    Matthew PollardAug 23, 2025
    Why does my ClimateMaster Heat Pump unit short cycle?
    • J
      James RodriguezAug 23, 2025
      If your ClimateMaster Heat Pump unit short cycles, it could be due to several reasons. A dirty air filter can cause short cycling, so check and clean it. Also, the unit might be in 'test mode'; reset the power or wait 20 minutes for it to automatically exit this mode. The unit might be oversized for the space; check the sizing for the actual load of the space. Finally, the compressor might be overloaded, so check it and replace it if necessary.
  • S
    Shelby GrantAug 26, 2025
    Why does only the fan run on my ClimateMaster Tranquility TTV026 Heat Pump?
    • B
      brittany67Aug 26, 2025
      If your ClimateMaster Heat Pump only runs the fan, it could be due to the following reasons: * Thermostat position: Ensure the thermostat is set for heating or cooling operation. * Unit lockout: Check for lockout codes and reset the power. * Compressor Overload: Check the compressor overload and replace it if necessary. * Thermostat wiring: Check the thermostat wiring at the heat pump. Jumper Y and R for compressor operation in test mode.
  • B
    Benjamin HowardAug 28, 2025
    What does LP/LOC Fault Code 3 mean on my ClimateMaster Tranquility TTV026 Heat Pump?
    • C
      Christina BarnesAug 28, 2025
      If your ClimateMaster Heat Pump is showing the LP/LOC Fault Code 3, indicating low pressure or loss of charge, it could be due to insufficient charge. Check for refrigerant leaks. Alternatively, the compressor might be pumping down at start-up, so check the charge and start-up water flow.
  • C
    Christine HorneAug 30, 2025
    Why does only the compressor run on my ClimateMaster Heat Pump?
    • E
      elizabethleeAug 30, 2025
      If your ClimateMaster Heat Pump only runs the compressor, it could be due to the following issues: * Thermostat wiring: Check the G wiring at the heat pump. Jumper G and R for fan operation. * Fan motor relay: Jumper G and R for fan operation. Check for Line voltage across BR contacts. * Fan motor: Check for line voltage at the motor and check the capacitor. * Reversing valve: Set for cooling demand and check 24VAC on RV coil and at CXM/DXM board. If the RV is stuck, run high pressure up by reducing water flow and while operating engage and disengage RV coil voltage to push valve. * Thermostat setup: Check for ‘O’ RV setup not ‘B’. * Thermostat wiring: Check O wiring at heat pump. Jumper O and R for RV coil ‘click’.
  • J
    joshua41Sep 2, 2025
    What does LT1 Fault Code 4 mean on my ClimateMaster Heat Pump?
    • D
      David AlexanderSep 2, 2025
      If your ClimateMaster Heat Pump displays the LT1 Fault Code 4, which indicates a water coil low temperature limit, it could be due to: * Reduced or no water flow in heating: Check the pump operation or water valve operation/setting. Also, check water flow and adjust to proper flow rate. Clean or replace any plugged strainer or filter. * Inadequate antifreeze level: Check the antifreeze density with a hydrometer. * Improper temperature limit setting: Clip JW3 jumper for antifreeze (10°F [-12°C]) use. * Water temperature out of range: Bring the water temperature within design parameters. * Bad thermistor: Check the temperature and impedance correlation per chart.
  • C
    Carly FowlerSep 5, 2025
    What does LT2 Fault Code 5 mean on my ClimateMaster Tranquility TTV026?
    • O
      Oscar Johnson MDSep 5, 2025
      If your ClimateMaster Heat Pump displays the LT2 Fault Code 5, indicating an air coil low temperature limit, it may be caused by: * Reduced or no air flow in cooling: Check for a dirty air filter and clean or replace it. Also, check the fan motor operation and any air flow restrictions. Ensure that the external static isn't too high. * Air temperature out of range: Ensure that the entering air temperature is within design parameters. * Improper temperature limit setting: Normal airside applications will require 30°F [-1°C] only. * Bad thermistor: Check the temperature and impedance correlation per chart.
  • A
    Amy BaxterSep 7, 2025
    What causes Condensate Fault Code 6 on my ClimateMaster Tranquility TTV026?
    • C
      Catherine BurkeSep 7, 2025
      If your ClimateMaster Heat Pump displays Condensate Fault Code 6, it could be due to several reasons: * Blocked drain: Check for blockage and clean the drain. * Improper trap: Check trap dimensions and location ahead of vent. * Poor drainage: Check for piping slope away from the unit and the slope of the unit toward the outlet. Also, check the vent location. * Moisture on sensor: Check for moisture shorting to the air coil. * Plugged air filter: Replace the air filter. * Restricted Return Air Flow: Find and eliminate the restriction. Increase return duct and/or grille size.
  • D
    Dawn BaileySep 10, 2025
    What does Over/Under Voltage Code 7 mean on my ClimateMaster Tranquility TTV026 Heat Pump?
    • T
      travis85Sep 10, 2025
      If your ClimateMaster Heat Pump displays the Over/Under Voltage Code 7, which auto-resets, it indicates a voltage issue. For Under Voltage, check the power supply and 24VAC voltage before and during operation, the power supply wire size, and compressor starting (consider a hard start kit). Also, check the 24VAC and unit transformer tap for correct power supply voltage. For Over Voltage, check the power supply voltage and 24VAC before and during operation, and the 24VAC and unit transformer tap for correct power supply voltage.
  • L
    Laura JenkinsSep 12, 2025
    What does Unit Performance Sentinel Code 8 mean on ClimateMaster Heat Pump?
    • B
      Becky HayesSep 12, 2025
      If your ClimateMaster Heat Pump displays Unit Performance Sentinel Code 8, it indicates a performance issue. If in heating mode and LT2 is greater than 125°F [52°C], check for poor air flow or an overcharged unit. If in cooling mode and LT1 is greater than 125°F [52°C] or LT2 is less than 40ºF [4ºC], check for poor water flow or air flow.

Summary

Model Nomenclature

General Information

Safety

Critical warnings and precautions for safe handling and operation.

Horizontal Installation

Horizontal Installation Details

Condensate Piping and Duct System Installation

Guidelines for condensate drainage and ductwork design.

Vertical Installation

Sound Attenuation and Condensate Piping

Methods for sound reduction and condensate drainage for vertical units.

Piping Installation

Ground-Water Heat Pump Applications

POE Oil and Piping Warning

Critical warning regarding POE oil incompatibility with PVC/CPVC piping.

Water Quality Standards

Electrical - Line Voltage

Electrical - Power Wiring

Electrical - Power & Low Voltage Wiring

Electrical - Low Voltage Wiring

Electrical - Thermostat Wiring

Blower Performance Data

ECM Blower Control

Typical Wiring Diagram - CXM;ECM (Single Phase)

Typical Wiring Diagram - ClimaDry (Single Phase)

Typical Wiring Diagram - CXM;ECM;MPC (DDC)

CXM Controls

CXM Control Overview and Selectable Inputs

General info on CXM control, test modes, and retry.

DXM Controls

DXM Control Overview and Selectable Inputs

General info on DXM control, test modes, and retry.

Safety Features - CXM and DXM Controls

CXM;DXM Control Safety Features Overview

General safety features protecting the compressor and components.

Control Operation and Diagnostics

Fault Codes and Diagnostic Features

Understanding fault codes and using diagnostic features.

Control Start-up Operation

Description of the control's start-up sequence.

ClimaDry Modulating Reheat Option

Sequence of Operation and Reheat Mode

How ClimaDry® operates and the reheat mode functionality.

UNIT STARTING AND OPERATING CONDITIONS

Environment, Power Supply, and Operating Limits

Requirements for installation environment, power, and operational limits.

Unit Starting and Operating Conditions

Commissioning Conditions

Specific conditions for initial unit commissioning and start-up.

Piping System Cleaning and Flushing

Cleaning and Flushing Procedure

Step-by-step guide for cleaning and flushing the piping system.

Flushing;Purging Units with ClimaDry

ClimaDry Flushing;Purging Procedure

Specific procedure for flushing and purging ClimaDry® equipped units.

Unit and System Checkout

Unit and System Checkout Steps

Comprehensive checklist for unit and system verification before operation.

Unit Start-Up Procedure

Unit Start-Up Procedure Steps

Detailed step-by-step instructions for starting the unit.

Operating Conditions and Option Corrections

Unit Operating Conditions and Corrections

Data on operating conditions and corrections for specific options.

Unit Operating Conditions

Preventive Maintenance

Functional Troubleshooting

Fault Codes and Troubleshooting Table

Comprehensive table of faults, causes, and solutions.

Specific Fault Troubleshooting

Troubleshooting common faults like power issues, pressure, and cycling.

Performance Troubleshooting

Insufficient Capacity Issues

Diagnosing and resolving insufficient cooling or heating capacity.

High Head Pressure and Low Suction

Troubleshooting high head pressure and low suction conditions.

Discharge Air and Humidity Issues

Addressing problems with discharge air temperature and humidity.

Warranty (U.S. & Canada)

Warranty (International)

ClimateMaster Tranquility TTV026 Series Specifications

General IconGeneral
CategoryHeat Pump
Cooling Capacity (BTU/h)26, 000
Cooling Capacity (tons)2.17
RefrigerantR-410A
Phase1
Compressor TypeScroll
ModelTTV026
Voltage208/230