Tranquility
®
30
(TT) Series
Models TTD/H/V 026 - 072
60 Hz - HFC-410A
INSTALLATION, OPERATION,
& MAINTENANCE
97B0075N05
Revised: 18 July, 2013
Table of Contents
Model Nomenclature 3
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
Electrical - Line Voltage 20
Electrical - Power Wiring 22
Electrical - Power & Low Voltage Wiring 23
Electrical - Low Voltage Wiring 24
Electrical - Thermostat Wiring 26
Blower Performance Data 27
ECM Blower Control 28
Typical Wiring Diagram - Units with CXM Board
and ECM Fan Motor (Single Phase) 30
Typical Wiring Diagram - Units with
ClimaDry
®
(Single Phase) 31
Typical Wiring Diagram - Units with CXM Board, 32
ECM Fan Motor, and MPC (DDC) CONTROLS
(SINGLE PHASE) 32
CXM Controls 33
DXM Controls 34
Safety Features - CXM and DXM Controls 36
ClimaDry
®
Modulating Reheat Option 38
Unit Starting and Operating Conditions 41
Piping System Cleaning and Flushing 42
Unit and System Checkout 44
Unit Start-Up Procedure 45
ClimaDry
®
II Option Corrections
(When Operating in Non-ClimaDry
®
Mode) 46
Unit Operating Conditions 47
Preventive Maintenance 49
Functional Troubleshooting 50
Performance Troubleshooting 51
Start-Up Log Sheet 52
Functional Troubleshooting 53
Warranty (U.S. & Canada) 54
Warranty (International) 55
Revision History 56

Questions and Answers

  • R
    Raymond WilsonAug 18, 2025
    How to troubleshoot main power problems in ClimateMaster Tranquility TTH038?
    • W
      Whitney GutierrezAug 18, 2025
      If your ClimateMaster Heat Pump has main power problems and the Green Status LED is off, check the line voltage circuit breaker and disconnect. Also, check for line voltage between L1 and L2 on the contactor, for 24VAC between R and C on CXM/DXM, and the primary/secondary voltage on the transformer.
  • C
    Cheryl JacobsAug 23, 2025
    Why does my ClimateMaster Heat Pump unit short cycle?
    • J
      Jason ReedAug 23, 2025
      If your ClimateMaster Heat Pump unit short cycles, it could be due to several reasons. A dirty air filter can cause short cycling, so check and clean it. Also, the unit might be in 'test mode'; reset the power or wait 20 minutes for it to automatically exit this mode. The unit might be oversized for the space; check the sizing for the actual load of the space. Finally, the compressor might be overloaded, so check it and replace it if necessary.
  • L
    Linda Allen MDAug 26, 2025
    Why does only the fan run on my ClimateMaster Heat Pump?
    • B
      butlerlauraAug 26, 2025
      If your ClimateMaster Heat Pump only runs the fan, it could be due to the following reasons: * Thermostat position: Ensure the thermostat is set for heating or cooling operation. * Unit lockout: Check for lockout codes and reset the power. * Compressor Overload: Check the compressor overload and replace it if necessary. * Thermostat wiring: Check the thermostat wiring at the heat pump. Jumper Y and R for compressor operation in test mode.
  • M
    Michelle MaldonadoAug 28, 2025
    What does LP/LOC Fault Code 3 mean on my ClimateMaster Heat Pump?
    • J
      Joseph RichardAug 28, 2025
      If your ClimateMaster Heat Pump is showing the LP/LOC Fault Code 3, indicating low pressure or loss of charge, it could be due to insufficient charge. Check for refrigerant leaks. Alternatively, the compressor might be pumping down at start-up, so check the charge and start-up water flow.
  • M
    Matthew ContrerasAug 30, 2025
    Why does only the compressor run on my ClimateMaster Heat Pump?
    • D
      Diane TurnerAug 30, 2025
      If your ClimateMaster Heat Pump only runs the compressor, it could be due to the following issues: * Thermostat wiring: Check the G wiring at the heat pump. Jumper G and R for fan operation. * Fan motor relay: Jumper G and R for fan operation. Check for Line voltage across BR contacts. * Fan motor: Check for line voltage at the motor and check the capacitor. * Reversing valve: Set for cooling demand and check 24VAC on RV coil and at CXM/DXM board. If the RV is stuck, run high pressure up by reducing water flow and while operating engage and disengage RV coil voltage to push valve. * Thermostat setup: Check for ‘O’ RV setup not ‘B’. * Thermostat wiring: Check O wiring at heat pump. Jumper O and R for RV coil ‘click’.
  • K
    Kevin StephensSep 2, 2025
    What does LT1 Fault Code 4 mean on my ClimateMaster Tranquility TTH038 Heat Pump?
    • J
      Jerry MurphySep 2, 2025
      If your ClimateMaster Heat Pump displays the LT1 Fault Code 4, which indicates a water coil low temperature limit, it could be due to: * Reduced or no water flow in heating: Check the pump operation or water valve operation/setting. Also, check water flow and adjust to proper flow rate. Clean or replace any plugged strainer or filter. * Inadequate antifreeze level: Check the antifreeze density with a hydrometer. * Improper temperature limit setting: Clip JW3 jumper for antifreeze (10°F [-12°C]) use. * Water temperature out of range: Bring the water temperature within design parameters. * Bad thermistor: Check the temperature and impedance correlation per chart.
  • T
    Tyler LeachSep 4, 2025
    What does LT2 Fault Code 5 mean on my ClimateMaster Heat Pump?
    • B
      Brandon ScottSep 4, 2025
      If your ClimateMaster Heat Pump displays the LT2 Fault Code 5, indicating an air coil low temperature limit, it may be caused by: * Reduced or no air flow in cooling: Check for a dirty air filter and clean or replace it. Also, check the fan motor operation and any air flow restrictions. Ensure that the external static isn't too high. * Air temperature out of range: Ensure that the entering air temperature is within design parameters. * Improper temperature limit setting: Normal airside applications will require 30°F [-1°C] only. * Bad thermistor: Check the temperature and impedance correlation per chart.
  • R
    Rachel CastroSep 7, 2025
    What causes Condensate Fault Code 6 on my ClimateMaster Tranquility TTH038 Heat Pump?
    • M
      Michelle LarsonSep 7, 2025
      If your ClimateMaster Heat Pump displays Condensate Fault Code 6, it could be due to several reasons: * Blocked drain: Check for blockage and clean the drain. * Improper trap: Check trap dimensions and location ahead of vent. * Poor drainage: Check for piping slope away from the unit and the slope of the unit toward the outlet. Also, check the vent location. * Moisture on sensor: Check for moisture shorting to the air coil. * Plugged air filter: Replace the air filter. * Restricted Return Air Flow: Find and eliminate the restriction. Increase return duct and/or grille size.
  • D
    David CopelandSep 10, 2025
    What does Over/Under Voltage Code 7 mean on my ClimateMaster Tranquility TTH038 Heat Pump?
    • T
      tjamesSep 10, 2025
      If your ClimateMaster Heat Pump displays the Over/Under Voltage Code 7, which auto-resets, it indicates a voltage issue. For Under Voltage, check the power supply and 24VAC voltage before and during operation, the power supply wire size, and compressor starting (consider a hard start kit). Also, check the 24VAC and unit transformer tap for correct power supply voltage. For Over Voltage, check the power supply voltage and 24VAC before and during operation, and the 24VAC and unit transformer tap for correct power supply voltage.
  • B
    Brian SanchezSep 12, 2025
    What does Unit Performance Sentinel Code 8 mean on ClimateMaster Tranquility TTH038?
    • W
      William SimpsonSep 12, 2025
      If your ClimateMaster Heat Pump displays Unit Performance Sentinel Code 8, it indicates a performance issue. If in heating mode and LT2 is greater than 125°F [52°C], check for poor air flow or an overcharged unit. If in cooling mode and LT1 is greater than 125°F [52°C] or LT2 is less than 40ºF [4ºC], check for poor water flow or air flow.

Summary

Model Nomenclature

General Information

Safety

General safety warnings, cautions, and notices for installation and servicing.

Pre-Installation

Steps and considerations before installing the unit, including checks and preparation.

Horizontal Installation

Horizontal Unit Location

Guidelines for selecting an indoor location for horizontal unit installation.

Mounting Horizontal Units

Instructions for suspending horizontal units using hanger kits and vibration isolators.

Field Conversion of Air Discharge

Horizontal Installation (cont.)

Vertical Installation

Vertical Unit Location

Guidelines for selecting a mechanical room or closet location for vertical unit installation.

Piping Installation

Installation of Supply and Return Piping

Guidelines for connecting water loop piping, including valve placement and hose selection.

Water-Loop Heat Pump Applications

Ground-Loop Heat Pump Applications

Open Loop - Ground Water Systems

Water Quality Standards

Guidelines for water quality parameters to ensure proper heat exchanger performance and longevity.

Ground-Water Heat Pump Applications

Water Quality Standards

Electrical - Line Voltage

Electrical - Power Wiring

Electrical - Power & Low Voltage Wiring

ECM Blower Control

Typical Wiring Diagram - CXM Board & ECM Motor

Typical Wiring Diagram - Units with ClimaDry

Typical Wiring Diagram - CXM, ECM, MPC (DDC) Controls

CXM Controls

DXM Controls

Field Configuration Options

Procedures for changing unit settings using jumpers and DIP switches on DXM controls.

Safety Features - CXM and DXM Controls

Anti-short cycle protection

Control feature that prevents compressor cycling within a 5-minute period.

Safety Features - CXM and DXM Controls (cont.)

ClimaDry Modulating Reheat Option

ClimaDry Sequence Of Operation

Describes the three modes of operation for heat pumps with ClimaDry® (cooling, reheat, heating).

ClimaDry Modulating Reheat Option (cont.)

Unit Starting and Operating Conditions

Piping System Cleaning and Flushing

Unit and System Checkout

UNIT CHECKOUT

Pre-power checks for water valves, wiring, and unit components.

SYSTEM CHECKOUT

Checks for system water temperature, pH, flushing, and control operation.

Unit Start-up Procedure

Functional Troubleshooting

Performance Troubleshooting

Insufficient capacity; Not cooling or heating

Troubleshooting steps for reduced performance in cooling or heating modes.

ClimateMaster Tranquility TTH038 Series Specifications

General IconGeneral
ModelTTH038
CategoryHeat Pump
Efficiency RatingHigh Efficiency
COP4.5
RefrigerantR-410A
Voltage208-230 V
Phase1
Compressor TypeScroll
Sound Level55 dB
Cooling Capacity38, 000 BTU/hr
Heating Capacity38, 000 BTU/h
Liquid Connection Size3/8 inch
TypeWater Source